July 2021
2/6
www.lifesafetypower.com
APPLICATION NOTE AN-05
Paxton NET2 ACCESS POWER
LOCK POWER
The NET2 controllers provide dry relay outputs for controlling locks. To provide power to the locks a D8, F8, C8, or M8 may be used as
shown below.
Locks Powered by a D8 Module
For the lowest-cost solution, the output relays of the NET2 modules may be used to directly control the locks, using a D8 for power. If
24V locks are being used, a separate 24V FPO power supply is required.
In single-voltage systems, each D8 output may be selected for constant, or FAI controlled voltage.
In dual-voltage systems, each D8 output may be selected for 12V or 24V.
12V
12V
FPO
12V
DC1
DC1 BR
BR
ISTAR PRO
GCM
LOCK
+ –
Connect to
NC for Fail Safe lock or
NO for Fail Secure lock
Connect to
NC for Fail Safe lock or
NO for Fail Secure lock
B1
B1
BR
BR
OUT X
OUT X
D8
+ –
NET2 Plus
NC
NC
NO
NO
COM
COM
Relay 1
Relay 1
DC1
DC1
DC2
DC2