16
Aircom Relays
The Aircom circuit board has three available “dry contact”
relays. Contact 3 is not available.
Contact 1
This relay is a dry contact (no power supplied from board).
The relay switches upon a call for heat.
This relay can be used to switch the heat demand signal for
boiler operation.
Power (if required) must be supplied to common from an
external source.
Max. Voltage
- 120 volts
Max. Amperage - 10 amps
Maximum 115V 10 amp resistive load.
T30
T29
T28
T43
SPARE
P2
P3
F2 MAX 2 amp
R
24Vac
D
efr
os
t
Fr
ee
ze
K7
K1
K2
K8
T3
1
T3
2
T3
3
T3
4
T3
5
T3
6
T3
7
T3
8
T3
9
T4
0
T4
1
T42
Contact 1
N.0. COM N.C. N.0. COM N.C. N.0. COM N.C. N.0 . COM
Contact 2
Contact 3
Contact 4
N.C
Boiler
Contact
T30
T29
T28
T43
SPARE
P3
MAX 2 amp
R
24Vac
D
efr
os
t
K7
K1
K2
K8
T3
1
T3
2
T3
3
T3
4
T3
5
T3
6
T3
7
T3
8
T3
9
T4
0
T4
1
T42
Contact 1
N.0. COM N.C. N.0. COM N.C. N.0. COM N.C. N.0 . COM
Contact 2
Contact 3
Contact 4
N.C
Humidifier
Contact
Contact 2 and 4
These relays are dry contacts (no power supplied from
board). The relays switch whenever the CAF blower motor
is operating.
These relays can be used to interlock Humidifiers, Air
Cleaning Equipment, etc.
Power (if required) must be supplied to common from an
external source.
Max. Voltage
- 120 volts
Max. Amperage - 10 amps
In order for any appliance to work properly it must be set
up and tested by a knowledgeable technician.
The following conditions must be met prior to
start-up
1. Ensure that connecting water lines are purged and free of
debris.
Caution: solder or other debris may cause the furnace
pump or check valve to malfunction.
2. Blower wheel rotates freely inside its housing.
3. Wiring connections are tight.
4. All duct and pipe connections are sealed.
5. Check that styrene block is removed from under pump.
6. Front access door is on tight.
7. Fan speed selection:
a)
Heating/Cooling
- factory setting is at high speed and
can be changed in the electrical box to medium-high or
medium if required.
Once the necessary connections have been made,
follow the Air Handler Start-Up Procedure:
1. Close shut-off valves separating the Air Handler from the
water heater.
2. Set up water heater according to manufacturer's instruc-
tions.
3. Purge air from unit. To do so, open the supply shut-off
valve to the furnace. Attach a garden hose to drain valve,
and drain water until you get a continuous flow. Close
the drain valve and purge the pump. To purge the air
from the pump, turn the large screw on the face of the
pump counterclockwise until water leaks out, then tight-
en. Open the supply shut-off valve.
4. Turn on power supply to Air Handler.
Caution: blower
may start to operate at low speed.
5. Switch the room thermostat to heat. The thermostat
should be set higher than the current room temperature in
order to energize the pump and commence the heating
cycle. (If the pump does not start, or the Air Handler is
not producing heat, refer to the Troubleshooting Section
in this manual.
6. Set room thermostat at desired temperature setting.
Start-Up Procedure