Page 10
A
IRCOM
R
ELAYS
&
I
NTERLOCKING TO A FURNACE
/
AIR HANDLER
The circuit board has three available “dry contact” relays. Contact 3 is not available.
Maximum 115V, 10 amp resistive load.
Contact 1
These relays initiate whenever the HRV is in defrost.
Contact 2 and 4
These relays initiate whenever the HRV fans are operating.
•
Use contact 2 or 4 to interlock the HRV to an Air Handler or Furnace.
Note:
Connecting the HRV as illustrated will ensure the Air Handler Blower Motor is operating
whenever the HRV is ventilating.
Caution
•
Consideration must be given to competing air flows when connecting the HRV in conjunction
with an Air Handler/Furnace Blower system.