SPECIFICATIONS
CORES
Modular (3 section) patented aluminum heat recovery cores arranged for
high efficiency cross-flow ventilation. Meets the flame spread and smoke
developed classifications of the National Building Code and NFPA 90A (1993
Edition).
MOTORS
Two PSC, 3 speed double shafted, 120 VAC, 3.95 Amps each (7.9 total on
high speed). HP - 1/4, 1625 RPM. Watts - total on high speed - 848.
FILTERS Washable air filters in exhaust and supply air streams.
BLOWERS
Each air stream has one double shafted motor driving 2 centrifugal blowers.
HYDRONIC REHEAT COIL
Standard built-in coil in both 1000RHC and 1000RHCAC. Rated 35,000 BTU
@ 140°F, 3 US gal./min. Design temperature drop is 20°F, fluid pressure drop
is 1.3 feet WG at rated flow, 3/4" fittings.
CONNECTION DUCT SIZES Five - 20" X 8" H (508 mm x 200 mm H).
DIRECT EXPANSION (DX) EVAPORATOR COIL (model 1000RHCAC
only) Factory installed 1.5 ton DX coil, 0.875" OD suction side, 0.625" OD
liquid side, built-in orifice.
MOUNTING
Two brackets under cabinet, connect to threaded rod type supports
(not included).
CASE
20 gauge prepainted galvanized steel (G60) for superior corrosion resistance.
Insulated with foil faced insulation where required to prevent exterior conden-
sation. Drain connections; two - 1/2" (12 mm) O.D.
CONTROLS
Illuminated power switch, 3 speed blower control, low voltage (24 VAC) termi-
nals to connect remote controls (not included), defrost light indicating
defrost/recirculation mode.
DEFROST CONTROLS
Supply bypass damper routes indoor air to defrost core.
WEIGHT 255 lbs.(116 Kg)
SHIPPING WEIGHT 280 lbs.(127 Kg)
1088 mm
(46 3/4")
200 mm
(8")
FRONT VIEW
1055 mm
(41 1/2")
508 mm
(20")
DISCHARGE SIDE
625 mm
(24 5/8")
INLET SIDE
DRAIN CONNECTION
COIL FITTINGS
508 mm
(20 ")
DIMENSIONS 1000RHC/RHCAC
mm (inches)
DEFROST &
RECIRCULATION
AIR
EXHAUST AIR
TO OUTSIDE
SUPPLY AIR
TO BUILDING
EXHAUST AIR
FROM BUILDING
SUPPLY AIR
FROM OUTSIDE
NOTE:
Service clearance
is 760 mm (30 in.)
508 mm
(20 ")
CONTROLS
149 mm
(5 7/8 ")
263 mm
(10 3/8 ")
263 mm
(10 3/8 ")
99-101
Sixty Minute Remote Timer
99-130
Remote Wall Mount Dehumidistat Control
24VAC only
All units conform to CSA and UL standards.
WARRANTY
Units carry a 15 year warranty on the heat recovery cores and
a 2 year replacement parts warranty.
TI-115
1203
AIRFLOWS (Each Air Stream)
613 (1300)
566 (1200)
518 (1100)
472 (1000)
423 (900)
378 (800)
329 (700)
282 (600)
235 (500)
AIRFLOW L/s (CFM)
25 (.1) 50 (.2) 75 (.3) 100 (.4) 125 (.5) 150 (.6) 175 (.7) 200 (.8)
EXTERNAL STATIC PRESSURE IN PASCALS (in. W.C.)
TOTAL CURRENT DRAW (AMPS) @ 120 VAC
7.8 MED
8.1 HIGH
7.1 LOW
70%
60%
50%
235
(500)
282
(600)
329
(700)
TEMPERATURE EFFECTIVENESS
AIRFLOW IN L/s (CFM)
NOTE: Exhaust Relative Humidity (RH) at 40%
EFFECTIVENESS
HIGH SPEED
HIGH SPEED
378
(800)
423
(900)
472
(1000)
566
(1200)
518
(1100)
PERFORMANCE
Performance data includes both reheat and DX coil installed.
Note there is little change in air flow with the DX coil removed.
Model 1000RHC and
Model 1000RHCAC
NOTE:
Hydronic reheat coil is designed to temper the ventilation air (after heat recovery) back to room temperature, and is not
intended for use as a primary heating source for the space.
•
Additional controls MUST be added to pump system (not included / not available from Nutech) feeding the coil to ensure
continuous water flow through it, and prevent freezing of the coil.
•
DX coil is designed to reduce humidity brought in from outside during ventilation. Coil MUST be connected to an outdoor
condensing unit (not included) by certified trades person. Not intended as a primary air conditioning system for the space.
DATE:_____________________________________________PROJECT: ________________________________________
MECHANICAL CONTRACTOR: __________________________________________________________________________
5