SURVEY

Sept 2021

4

Model:

HFO/E 2,5kVA 

230V

Condition:

The inverter has to be used at maximum load in a higher ambient temperature.

Symptoms:

Inverter might stop after approximately 45 minutes.
After some time the inverter starts again when switching On.

Causes:

Electronic inverter measures a too high temperature.  (protection mode will be activated)
Insufficient aircooling inside inverter housing.

Solution:

Improve air flow inside yellow housing.

Adaptions:

Create air inlet holes on bottom side.
Place protective strip
Add cooling fan.

Materials:

Replacement panel with hole for cooling fan.     (available in kit. No. 145400)
Protective strip to cover air inlet holes

Tools:

Screwdrivers:  Ph2 / Slotted 8mm / Wrench 13