Product/System Description
3.2
Introduction
The Liebert XDO is an overhead cooling system designed for installation above heat-dissipating
equipment. A fan draws hot air exhausted from the equipment through two cooling coils and dis-
charges cool air back down to the equipment (see
). The system consists of XDO modules,
XDP/XDC coolant distribution units, power and signal cabling and interconnecting piping (see
).
Liebert’s XDP/XDC monitors room conditions and prevents coil condensation by maintaining the tem-
perature of the coolant pumped to the XDOs above the room dew point.
Figure 3
Generic air flow schematic
Figure 4
Generic piping schematic
HOT AISLE
Cold Aisle
Spacing
Hot air is
drawn into
the XDO
for cooling
XDO
XDO
Critical
Equipment
Critical
Equipment
Critical
Equipment
Critical
Equipment
COLD AISLE
Hot air goes
into the hot
aisle
Cooled air
enters the
rack...
Hot air goes
into the hot
aisle
Cooled air
enters the
rack...
COLD AISLE
Liebert
XDC
Coolant
Chiller
XDO/XDV
XDO/XDV
XDO/XDV
XDO/XDV
XDCoolant
XDCoolant
Liebert
Heat
Rejection
Liebert
XDC
Coolant
Chiller
XDC pumps coolant
to XDO modules and also
isolate coolant from build-
ing chilled water supply.
Return Lines
Supply Lines