UPStation GXT 3x1
Chapter 7 – Specification
(06/02)
Page 23
7
SPECIFICATIONS
SPECIFICATIONS
MODEL NUMBER
GXT3X1 - 6000
GXT3X1 - 8000
GXT3X1 - 10000
MODEL RATING VA/W (max)
6000 / 4200
8000 / 5600
10000 / 7000
DIMENSIONS: mm (in)
Unit
W x D x H
340 x 650 x 960
(13.4 x 25.6 x 37.8)
Shipping
W x D x H
510 x 840 x 1235
(20.1 x 33.1 x 48.6)
WEIGHT: kg (lbs)
Unit
172
224
Shipping
227 (500)
284 (626)
MECHANICAL CHARACTERISTICS
Protection grade
IP 31
Colour
RAL 9002
INPUT AC PARAMETERS
Nominal Voltage (typical)
230 VAC nominal (L-N)
400 VAC nominal (L-L)
100% - 90% Loading
186 VAC to 280 VAC ± 5% (L-N)
322 VAC to 485 VAC ± 5% (L-L)
90% - 0% Loading
159 VAC (L-N) to 280 VAC ± 5% (L-N)
275 VAC to 485 VAC ± 5% (L-L)
Frequency
46.6 - 52.4 or 57.1 - 62.9 Hz
±0.1 HZ; auto sensing
OUTPUT AC PARAMETERS
Voltage
208/220/230/240 VAC (switch selectable); ±3%
Frequency
50 Hz or 60 Hz; auto sensing
Waveform
Sinewave
Main Mode Overload
112% to 130% for 10 seconds minimum
131% to 200% for 8 cycles min.;
>201% for 96 msec min. with transfer to bypass
BYPASS PARAMETERS
Default Acceptable Input Voltage
for transfer to BYPASS
Nominal ±15%. (User selectable)
Default Acceptable Input
Frequency for transfer to
BYPASS
Same as 50/60 Hz output frequency synchronization range
Bypass Overload Protection
Characteristic (Circuit Breaker)
200%: 10 sec<trip time<100 sec
1000%:5 msec<trip time<3 sec
BATTERY PARAMETERS
Type
Valve-regulated, nonspillable, lead acid
Qty. x Voltage x Rating
20 x 12V x 7.0 Ah
40 x 12V x 7.0 Ah
Back-up Time
7 min. minimum
13 min. minimum
10 min. minimum
Recharge Time
(Internal Batteries Only)
3 hours to 80% capacity after full discharge into 100% load
ENVIROMENTAL
Operating Temperature
0° C to +40° C (+32° F to +104° F)
Storage Temperature
-15° C to +50° C (+5° F to +122 °F)
Relative Humidity
0% to 95%, non-condensing
Operating Elevation
Up to 3000 m (10,000 ft.) at 40° C without derating
Storage Elevation
15.000 m (50,000 ft.) maximum
Audible Noise
<65 dBA at 1 metre
AGENCY
Safety
EN50091-1-1:1996; CE Low Voltage Directive
EMI/EMC
EN50091-2:1995 Class A; CE EMC Directive
Immunity
EN50091-2 (IEC 801-2, 3, 4, 5)
Содержание UPSTATION GXT3X1-10000
Страница 2: ...D D DR R R...
Страница 4: ...UPStation GXT 3x1 USER MANUAL Page iv 06 02...
Страница 8: ...UPStation GXT 3x1 USER MANUAL Page viii 06 02 7 SPECIFICATIONS 23 7 1 Limited Warranty 24...
Страница 18: ...Chapter 2 Installation UPStation GXT 3x1 Page 10 06 02 This page is left blank intentionally...
Страница 30: ...Chapter 6 Troubleshooting UPStation GXT 3x1 Page 22 06 02 This page is left blank intentionally...