Chapter 8 Options 59
Liebert
®
ITA 10kVA UPS User Manual
Control port
Input switch
Battery port
AC input
Ventilation hole
AC input amplified
Power linker
(with sliding panel)
Slide
Button
PP30 terminal
Figure 8-16 Rear panel of 10A charger
警告
危 险
Note
Unauthorized personnel are prohibited from opening the cover of the 10A charger.
8.8 Assembly Of LCD Display Panel
UF-LCD-ITA-0100 is an option for LCD display panel of the ITA 10kVA UPS, and its commissioning has been
completed before delivery. You need to install the assembly of the LCD display panel corresponding to the UPS.
Refer to
4.2 LCD Display Panel
for the menu structure, function description and interface of the LCD display panel
assembly. The appearance of the LCD display panel assembly is shown in Figure 8-17.
Figure 8-17 Appearance of LCD display panel assembly
The LCD display panel has been installed before delivery. If you need a LCD display panel (optional), remove the
LED display panel first, and then install the LCD display panel.
警告
危 险
Note
Before replacing the display panel, you must ensure that the UPS has been powered off, the bypass MCB, input MCB and
external output MCB are open.
The replacement procedures are as follows:
1. Make sure that the UPS is powered off, bypass MCB and I/O MCBs are open, and the battery cables has been
disconnected.
2. Press the two ends of the UPS plastic panel by hand, gently pull the plastic panel outwards to remove it, as shown
in Figure 8-18 (a).