Maintenance

23

10.3.1 Internal Battery Replacement Procedure

1. Gently remove the front plastic bezel cover from the UPS.
2. Loosen and remove the five (5) screws on the front cover plate. Lay the cover plate aside for 

reassembly.

3. Loosen and remove four (4) screws on battery bracket.
4. Disconnect the two (2) slotted, red and black battery connectors.
5. Grasp the battery pack assembly by the pull tab and pull it out of the front of the UPS.
6. Unpack the new battery assembly, taking care not to destroy the packing. Compare new and old 

battery assemblies to make sure they are the same. If so, proceed with 

Step 7

; otherwise STOP 

and contact your local dealer, Liebert representative, or the Liebert Worldwide Support Group.

7. Slide in the new replacement battery pack.
8. Reattach the battery bracket with the four (4) screws.
9. Reconnect the two (2) slotted red and black battery connectors.
10. Reattach the front battery door with the five (5) screws.
11. Reattach the front plastic bezel cover to the UPS.

Figure 19 Battery replacement procedure

0001

0203

Front Plastic Bezel

Cover 

Plate

Battery 

Bracket

Battery

Connectors

Battery 

Pull Tab

Содержание PowerSure PSI 1000 - 3000VA 60 Hz 120V

Страница 1: ...Power Protection for Business Critical Continuity Liebert PowerSure PSI User Manual 1000 3000VA 60 Hz 120V...

Страница 2: ......

Страница 3: ...nly 7 4 0 WHAT S INCLUDED 8 5 0 INSTALLATION 9 5 1 Preparation 9 5 2 Tower UPS Installation 9 5 3 Rack Mount UPS Conversion and Installation 10 5 4 External Battery Cabinet Installation 13 6 0 CONTROL...

Страница 4: ...Battery Mode Shutdown Via Pins 4 5 19 8 3 USB Interface Port 20 8 4 Data Line Protection Connectors 20 8 5 UPS Intelligent Communications 20 9 0 VOLTAGE PROGRAMMING PROCEDURE 21 10 0 MAINTENANCE 22 1...

Страница 5: ...assemblies 11 Figure 11 REPO switch connections 13 Figure 12 Load level indicators 4 green 1 amber 15 Figure 13 Battery level indicators 5 green 15 Figure 14 Normal mode operation with 26 50 load 17 F...

Страница 6: ...iv...

Страница 7: ...ve even when AC power is disconnected For service contact a qualified technician CAUTION Although your UPS has been designed and manufactured to ensure personal safety improper use can result in elect...

Страница 8: ...cordance with local regulations NOTE This device complies with part 15 of the FCC Rules Operation is subject to the following two conditions 1 This device may not cause harmful interference and 2 this...

Страница 9: ...tion followed by important instructions Requests the user to consult the manual Indicates the unit contains a valve regulated lead acid battery Recycle DC voltage Equipment grounding conductor Bonded...

Страница 10: ...e utility Sensitive electronic equipment operates best from sinewave power For ease of use the PowerSure PSI contains Status Indicators to display Load Level Battery Level Buck Boost Over Temperature...

Страница 11: ...C 72V 30A 1 2 3 4 INTELLISLOT 15A 120VAC LOAD 2 BREAKER LOAD 1 BREAKER IN OUT REPO RS 232 Data Line Connectors Circuit Breaker USB Port RS232 DB 9 Port Intellislot Port Attached Power Cord 10ft 3m REP...

Страница 12: ...uency interference RFI They minimize surges or interference present in the utility line and keep the sensitive equipment protected 3 2 Relay In Normal mode the Relay passes utility AC power to the con...

Страница 13: ...ets are available to extend battery run times 3 6 Inverter 1000 1440 Models Only In battery mode operation the inverter utilizes the DC output of the battery and inverts it into pre cise regulated sin...

Страница 14: ...e 10 ft 3m USB cable 6 ft 1 8m RJ 11 cord 7 ft 2 1m Rack mount handles Support base Fixed rails Mounting hardware screws washers Front bezel Vertical display overlay MultiLink software CD RJ 11 cord 7...

Страница 15: ...e instructions in either Tower UPS Installation or Rack Mount UPS Conversion and Installation 5 2 Tower UPS Installation When using the PowerSure PSI in a tower configuration use the included support...

Страница 16: ...nt the UPS or battery cabinet Make sure fixed rails are at the same mounting height on each of the four 4 rack mounting rails NOTE When rack mounted the UPS must be supported by a shelf slide rails br...

Страница 17: ...e front of the UPS to rack mounting rails to prevent the UPS from sliding out of position 11 Plug the PowerSure PSI s attached 10 ft 3m power cord into a dedicated wall receptacle properly protected b...

Страница 18: ...r computer The PSI will work automatically with your built in power management software on Windows XP and 2000 and Mac OS 10 2 or later see 8 3 USB Interface Port for details Option 4 Intellislot The...

Страница 19: ...cluded with the UPS for the tower option to prevent tip over One additional set of support base spacers ships with each external battery cabinet 5 Connect the supplied external battery cabinet cable t...

Страница 20: ...will remain silenced until a new alarm condition is detected Battery Test To initiate a manual battery test press the ON Alarm Silence Battery Test button for at least one second while operating from...

Страница 21: ...de The Battery Level Indicators are displayed in 20 increments as shown in Figure 13 Figure 13 Battery level indicators 5 green The PowerSure PSI is equipped with automatic and remote battery test fea...

Страница 22: ...UPS detects an over temperature condition This indicator illuminates when the UPS shuts down due to an over temperature condition see Troubleshooting section for details 6 10 Fault Indicator Red The...

Страница 23: ...the UPS is switched Off By default the UPS is set to perform an automatic battery test after it has been operating continuously for two 2 weeks The automatic battery test can be disabled via MultiLink...

Страница 24: ...w battery condition occurs the Battery Indicator flashes green and the alarm sounds every half second The default low battery warning is two 2 minutes but can be configured via MultiLink For more info...

Страница 25: ...nd 5 of the DB 9 connector 8 2 1 Any Mode Shutdown Via Pins 5 6 When Pin 6 is shorted to Pin 5 the UPS output is shut Off regardless of what mode the UPS is oper ating in The UPS cannot be started as...

Страница 26: ...tionally MultiLink can be configured to coordinate shutdown across the network with other computers running MultiLink when you purchase a MultiLink License Kit For more information about the Intellisl...

Страница 27: ...nitially the 0 25 Load Level Indicator will be flashing indicating the default setting of 120V as shown in Figure 18 5 Press the ON button to step through the voltage settings until the appropriate Lo...

Страница 28: ...teries 10 3 Battery Replacement CAUTION A battery can present a risk of electrical shock and high short circuit current The following precautions should be observed before replacing the batteries Remo...

Страница 29: ...ssembly taking care not to destroy the packing Compare new and old battery assemblies to make sure they are the same If so proceed with Step 7 otherwise STOP and contact your local dealer Liebert repr...

Страница 30: ...alarm sounds alerting that the UPS requires attention The alarm can be silenced except for low battery overload warning and over temperature warning conditions 2 One or more additional indicators will...

Страница 31: ...Indicator Lit continuous beep Contact your local dealer Liebert representative or the Liebert Worldwide Support Group UPS shutdown due to a command from the communications port s Load Level 0 25 Indi...

Страница 32: ...5 15R 8 NEMA 5 15R 6 NEMA 5 15 R 2 NEMA 5 20 R T Slot accepts 15APlug 6 NEMA 5 15 R 2 NEMA 5 20 R T Slot accepts 15APlug 4 NEMA 5 15 R 2 NEMA 5 20 R T Slot accepts 15A Plug 1 NEMA L5 30 R Voltage Norm...

Страница 33: ...x 430 3 43 x 24 1 x 17 87 x 612 x 430 Shipping 11 8 x 27 8 x 23 5 300 x 706 x 598 13 1 x 34 x 23 5 333 x 864 x 598 Weight lbs kg Unit 66 1 30 101 4 46 Shipping 85 1 38 6 118 1 53 6 Battery Parameter T...

Страница 34: ...493 444 20 409 283 307 291 249 30 283 219 243 222 168 40 248 177 197 194 148 50 209 133 163 150 129 60 166 122 141 137 114 70 136 98 128 122 92 80 127 84 115 107 71 90 110 64 102 92 56 100 98 56 89 7...

Страница 35: ...or warranty protection visit the Quick Links section of our Web site at www liebert com Click on Product Warranty Registration and complete the form If you have any questions please contact us at US 8...

Страница 36: ...ert Corporation assumes no responsibility and disclaims all liability for damages resulting from use of this information or for any errors or omissions 2006 Liebert Corporation All rights reserved thr...

Отзывы: