PowerSure PSA

Guide Specification

350 – 1000VA

SL-23271 8/03

5

1.7

QUALITY ASSURANCE

1.7.1

Manufacturer Qualifications

Liebert Corporation provides more than twenty years experience in the design, manufacture, and
testing of solid-state UPS systems and the company is certified to ISO 9001.

1.7.2

Factory Testing

Before shipment, the product is tested to assure compliance with the specification.  

2.0

PRODUCT

2.1

FABRICATION

All materials and components making up the UPS are new, of current manufacture, and have not been in
prior service except as required during factory testing. All relays are provided with dust covers.

2.1.2

Wiring

Wiring practices, materials, and coding are in accordance with the requirements of the standards
listed in section 1.2.  All wiring is copper.

2.1.3

Cabinet

The UPS unit comprised of: TVSS & EMI/RFI Filters, Bi-Directional Converter, Automatic
Voltage Regulator and Battery consisting of the appropriate number of sealed battery cells; is
housed in a mini-tower NEMA type 1 enclosure.  The UPS cabinet is injection-molded standard
color.  Dimensions and weights are:

UNIT

UNIT DIMENSIONS

W x D x H in  (mm)

120 VAC UNITS

WEIGHT

lbs  (kg)

230 VAC UNITS

WEIGHT

kg (lbs)

350VA

4.6 x 7.7 x 8.7  (116 x 196 x 222)

16.8  (7.6)

7 (15.4)

500VA

4.6 x 7.7 x 8.7  (116 x 196 x 222)

17.2  (7.8)

7.4 (16.3)

650VA

4.6 x 14.1 x 8.7  (116 x 358 x 222)

20.7  (9.4)

9.1 (20.1)

1000VA

4.6 x 14.1 x 8.7  (116 x 358 x 222)

29.7  (13.5)

13.2 (19.1)

2.1.4

Cooling

The UPS is convection cooled.

2.2

COMPONENTS AND OPERATION

2.2.1

Input Protection

The UPS has built-in protection against undervoltage, overcurrent, and overvoltage conditions
including low-energy lightning surges introduced on the primary input power source. The UPS is
provided with an input circuit protector. The 120 VAC UPS models withstand input surges
without damage per criteria listed in IEEE C62.41, Category A, Level 3 and the 230 VAC UPS
models withstand input surges without damage per criteria listed in EN61000-4-5, Level 3,

Criteria A

.  Additionally, the UPS is supplied with one pair of Data Line Protection Connectors

to provide phone, fax or modem line surge protection via RJ-45 connectors.  These Data Line
Protection Connectors provide transmission for 10/100 Base-T Ethernet connection.

Содержание PowerSure PSA 350VA to 1000VA

Страница 1: ...herein the statements in this specification will govern 120V Units UL 1778 c UL listed to CSA 22 2 No 107 1 FCC Part 15 Subpart B Class B ANSI C62 41 Category A Level 3 IEEE 587 Category A EN61000 4 5 Level 3 Criteria A EN61000 4 2 Level 3 Criteria A EN61000 4 3 Level 3 Criteria A EN61000 4 4 Level 4 Criteria A EN61000 4 6 Level 3 Criteria A EN61000 3 2 EN61000 3 3 ISTA Procedure 1A 230V Units EN5...

Страница 2: ... specifications of the UPS are Input 120V Units 0 160 VAC 60 50 Hz auto sensing single phase 2 wire plus ground 230V Units 0 300 VAC 50 60 Hz auto sensing single phase 2 wire plus earth Output 120V Units 110 120 127 VAC 10 60 50 Hz single phase 2 wire plus ground DIP Switch selectable 230V Units 220 230 240 VAC 10 50 60 Hz single phase 2 wire plus earth DIP Switch selectable B Output Load Capacity...

Страница 3: ...its can withstand input surges of up to 570J without damage per criteria listed in IEEE C62 41 Category A Level 3 The 230 VAC units can withstand input surges of up to 660J without damage per criteria listed in EN61000 4 5 Level 3 Criteria A D Input Connections The 120 VAC units have an attached input cord 6 0 feet 1 8 meters in length measured between the inside edges of the connectors The attach...

Страница 4: ...xceed 40dB when measured at 1 meter from the surface of the UPS A weighted E Electrostatic Discharge The 120 VAC units are able to withstand an electrostatic discharge compliant to EN61000 4 2 level 3 Criteria A without damage and without affecting the connected load The 230 VAC units are able to withstand an electrostatic discharge compliant to EN61000 4 2 level 3 Criteria A without damage and wi...

Страница 5: ...e UPS cabinet is injection molded standard color Dimensions and weights are UNIT UNIT DIMENSIONS W x D x H in mm 120 VAC UNITS WEIGHT lbs kg 230 VAC UNITS WEIGHT kg lbs 350VA 4 6 x 7 7 x 8 7 116 x 196 x 222 16 8 7 6 7 15 4 500VA 4 6 x 7 7 x 8 7 116 x 196 x 222 17 2 7 8 7 4 16 3 650VA 4 6 x 14 1 x 8 7 116 x 358 x 222 20 7 9 4 9 1 20 1 1000VA 4 6 x 14 1 x 8 7 116 x 358 x 222 29 7 13 5 13 2 19 1 2 1 ...

Страница 6: ... 2 2 3 Bi Directional Converter DC Protection The following DC shutdown levels protect the UPS DC Overvoltage Shutdown DC Undervoltage Shutdown End of Discharge DC Undervoltage Warning Low Battery Reserve 2 2 2 4 Output Protection For output faults including short circuits and overloads the UPS is protected by the input circuit protector during Normal mode and by electronic current limiting during...

Страница 7: ... than 0 5 sec will start up the UPS and to turn the UPS off the button will need to be depressed for more than 2 sec 2 2 3 4 On Line Battery Test The UPS is provided with an automatic biweekly battery test feature The test ensures the capability of the battery to supply power to the inverter while loaded If the battery fails the test the UPS will display a warning to indicate the batteries need re...

Страница 8: ...on settings This shutdown signal 5 12VDC must have a duration of at least 1 5 seconds for the UPS to be shut down The UPS communicates via serial communications using Liebert ESP II protocol The PowerSure PSA has a USB interface port for communication that will work with the built in Microsoft Power Manager software on the user s PC if the PC is so equipped It will provide UPS status and manages t...

Отзывы: