The Liebert

®

 GXT3

 500-3000 VA models ship with the internal battery installed.  Locate the plastic bezel from the 

shipping box and attach the bezel to the UPS taking care to align the fastening clips on both ends before inserting them 
into the holes. 
 
If your application requires the use of external battery cabinets for longer back up time requirements, connect the first 
battery cabinet to the UPS with the cable provided with the battery cabinet.  

Note: it does not matter which connector is 

used on the battery cabinet

.  If more than one battery cabinet is used the additional cabinets then connect to the adjoining 

battery cabinet. 
 
To complete the installation of the UPS, simply connect the input plug on the attached 10 foot input cord to the proper wall 
receptacle per the following table.  

 Note: the 500-2000VA UPS models will now have power and the AC Input indicator on 

the display should illuminate.  The UPS will also begin to charge the internal batteries at this point, so there will also be 
battery capacity LEDs illuminated.

 

 

UPS Model 

Recommended 
External Over 
Current Protection 

NEMA Input Plug 
Provided 

NEMA Input Plug 
Provided 

GXT3-500RT120 
GXT3-700RT120 
GXT3-1000RT120 
GXT3-1500RT120 
 
GXT3-1000MT120 

15A 

5-15 

 

GXT3-2000RT120 

20A 

5-20 

 

GXT3-3000RT120 

30A 

L5-30 

 

GXT3-3000RT208 

20A 

L6-20 

 

 
The Liebert GXT3 UPS is ready to be powered.   

1.  If an optional MicroPOD was used, ensure that the maintenance bypass switch is in the UPS position. 
2.  Install any optional Intellislot communication card into the Intellislot port on the rear of the unit. 
3.  Ensure the input breaker in the panelboard that provides input power to the UPS is closed 
4.  For 3000 VA models only, close the input breaker on the rear of the UPS unit.

 Note: the UPS will now have power 

and the AC Input indicator on the display should illuminate.  The UPS will also begin to charge the internal 
batteries at this point, so there will also be battery capacity LEDs illuminated.

 

5.  The Liebert GXT3 UPS has customizable settings that might be required depending on the application.  Please 

review the CD that ships with the UPS unit for the steps to use the configuration program and make any 
necessary changes.  Once that is complete, proceed to the next step. 

6.  If external battery cabinets are used, close all breakers on the rear of each battery cabinet 
7. 

Press and hold for about 4 seconds, the “ON” button on the UPS display.  

Note: this will apply power to the output 

receptacles via the internal bypass and the bypass indicator will be illuminated along with an audible beep

.   

8.  Over the next several seconds the UPS will perform the self checks and startup routine then automatically 

transfer the connected equipment to the inverter power.  Once that is complete, the bypass indicator will turn off 
and the inverter indicator will illuminate.   

 
The UPS is now running in normal operation mode providing protected, filtered power to the connected equipment. 

 
 

 