Operation with Advanced Microprocessor Controls
14
2.8.2 Non-Volatile Memory
All critical information is stored in nonvolatile memory. Setpoints, setup parameters, and component
run hours are kept inside the microcontroller in EEPROM. Information retained for the alarm history
is kept in non-volatile RAM.
2.8.3 DIP Switches
Equipment options are selected and enabled using DIP switches 1 through 7. These are located at the
upper left of the control board and are labeled SW1. Switch 1 is at the top. These switches are factory
set and should not require any user changes. The setting and function of the switches can be read
from the LCD display (see
Show DIP Switches on page 8
or the accompanying
Table 4
).
2.8.4 Control Outputs
Active control outputs are indicated with LEDs on the lower section of the control board. Each LED is
lit if the control output is active (on). The LEDs assist in troubleshooting the system. Refer to the fol-
lowing table.
Table 6
Control output LEDs
LED
Control Output
R5
Heat Rejection
LLSV
Liquid Line Solenoid Valve
HGBP
Hot Gas By-Pass or Compressor Unloader Valve
C1
Compressor
RH1
Reheat Stage 1, Hot Gas, Hot Water Reheat Solenoid or SCR Reheats
RH2
Reheat Stage 2
HUM
Humidifier
FAN
Main Fan
HMV
Humidifier Make-Up Valve
LLSV2
Part Coil Solenoid Valve
Содержание CHALLENGER 3000
Страница 2: ......
Страница 8: ...vi ...
Страница 74: ...Semiannual Maintenance Inspection Checklist 66 ...
Страница 75: ......