Liberty Pumps SX34-3-131 Скачать руководство пользователя страница 3

Mounting the Control Panel

1. 

Determine  mounting  location  for  panel.  If 

distance exceeds the length of either the float 

switch cables or the pump power cables, 

splicing will be required. For outdoor or wet 

installation, we recommend the use of a SJE-

Rhombus

®

 liquid-tight junction box with liquid-

tight connectors to make required connections. 

You must use conduit sealant to prevent 

moisture or gases from entering the panel.

2. 

  Mount control panel with mounting devices 

furnished.

3.

   Determine  conduit  entrance  locations  on 

control panel.  

 NOTE:

 Be sure the incoming power, voltage, 

amperage, and phase meet the requirements 

of the pump motor being installed. If in doubt, 

see the pump identification plate for electrical 

requirements.

4.

   Drill proper size holes for type of connectors 

being used.

 NOTE:

 If using conduit, be sure that it is of 

adequate  size  to  pull  the  pump  and  switch 

cables through.

5.

   Attach cable connectors and/or conduit 

connectors to control panel.

FOR INSTALLATION WITHOUT 

A SPLICE, GO TO STEP 10; 

FOR INSTALLATION REQUIRING  

A SPLICE, FOLLOW STEPS 6-9.

6.

   Determine location for mounting junction box 

according to state and local code requirements. 

Mount junction box to proper support.

7.

   Run conduit to junction box. Drill proper size 

holes for the type of conduit used. Attach 

connectors to junction box.

Installation Instructions

8.

   Identify and label each wire before pulling 

through conduit into control panel and junction 

box. Make wire splice connections at junction 

box.

9.

   Firmly tighten all fittings on junction box.  

10.

 If a junction box is not required, pull cables 

through conduit into control panel.

11.

 

Set motor protective switch:

  a) set the dial to match motor full load amps

  b) turn dial on motor protective switch to 

the ON position

 

  NOTE: Resetting the dial with power applied 

to the motor protective switch could start 

the motor.

12.

  Connect pump wires directly to the motor 

contactor terminal positions T1, T2, and T3.  

 

 

NOTE:

 Three phase motors will run in either 

direction. Check pump motor before installation 

for proper rotation. To correct rotation, change 

pump cable connections on any two terminals 

T1-T2-T3.

13.

    Connect  “power-in”  conductors  to  proper 

locations: 208/240/480 on 3 position terminal 

block. 

Install tagged factory wire to 

appropriate transformer primary voltage 

tap.

VERIFY CORRECT OPERATION OF 

CONTROL PANEL AFTER 

INSTALLATION IS COMPLETE.

Operations

Three phase simplex control panels are designed 

to  operate  in  a  three  float  system  as  standard. 

When all floats are in the open or OFF position, 

the panel is inactive. As the liquid level changes 

and closes the stop float, the panel remains inac

-

tive until the start float also closes. At this point 

the pump will start, assuming the HOA switch is in 

the AUTOMATIC mode and the power is ON. The 

pump will remain ON until both the stop and start 

floats open (return to the OFF position). If the liquid 

level travels beyond both the stop and start floats 

and reaches the alarm float, the audio/visual alarm 

will be activated. The alarm horn can be silenced 

by pressing the silence switch.

Alarm System (Horn and Indicator)

When an alarm condition occurs, a red light and 

a horn will be activated. If the test/normal/silence 

switch is moved to the silence position, the horn will 

be silenced. When the alarm condition is cleared, 

the alarm system is reset. The alarm system can 

be tested by moving the test/normal/silence switch 

to the test position.

HOA Switch

A hand-off-automatic switch is provided for the 

pump. In the hand mode, the pump will turn on 

unless other safety features are employed. In the 

automatic mode, the pump will turn on from com-

mands by the float switches.

Motor Protective Switch

A motor protective switch is supplied for the pump 

to provide an adjustable overload, branch circuit 

protection and disconnect. The overload must be 

set in the field. To set the overload, dial the amp 

scale to the pump’s full load amps (FLA). If the 

FLA’s are unknown, use a calibrated amp me-

ter to measure the pump amperage draw under 

loaded conditions. An auxiliary contact is wired in 

series with the magnetic contactor coil so that on 

an overload trip, the magnetic contactor will be 

disabled. In the event of an overload trip, the mo-

tor protective switch must be reset by first turning 

the handle counterclockwise to the OFF position 

and then turning the handle 90

o

 clockwise to the 

ON position.

Pump Run Light

The run light will be ON in either the hand or the 

automatic mode when the pump is called to run.

Control Power Light

Light will illuminate when the control circuit has 

power.

Alarm Power Light

Light will illuminate when the alarm circuit has 

power.

Alarm Fuse

Provides alarm circuit protection and provides a 

means of disconnecting alarm circuit power.

Control Fuse

Provides control circuit protection and provides a 

means of disconnecting control circuit power.

Dry Auxiliary Contacts (optional)

Normally open

 - Contacts are open under normal 

conditions and closed when alarm condition is 

present.  

Normally closed

 - Contacts are closed under 

normal conditions and open when alarm condition 

is present.  

Both types automatically reset once alarm condi-

tion is cleared.

Seal Failure Circuit and Indicator Light 

(Optional)

The seal fail circuit has resistance sensitivity and 

will sense the presence of water in the pump seal 

chamber. Upon installation, turn the sensitivity dial 

on the seal fail module to the point where the light 

turns on, then dial back slowly until the light turns 

off. If water enters the seal chamber at this point, 

the seal chamber circuit will sense a change in 

resistance. After a short time delay, the indicator 

light will turn on.  When the condition is cleared, the 

relay will de-energize and the indicator light will turn 

off. The seal fail relay has a sensitivity adjustment 

so that false readings may be tuned out.

Thermal Cutout (Optional)

The thermal cutout circuit is wired in series with 

the magnetic contactor coil. If the pump’s thermal 

switch opens on high temperature, the magnetic 

contactor will turn off and stop the pump. When 

the thermal switch cools and closes, the magnetic 

contactor will turn on if the pump is called to run. 

NOTE:

 Some options ordered may not be included 

in this manual.

- 3 -

- 4 -

7227000B

7227000B

Отзывы: