background image

6850000D

Copyright © Liberty Pumps, Inc. 2021 All rights reserved.

5 | EN

Pump Design

XLSG/XLSGX-Series grinder pumps are designed for continuous 

underwater operation. The motor and pump form a close coupled, 

watertight unit. The induction motor is insulated against heat and 

moisture in accordance with Class F 311°F (155°C) regulations.
The motor is protected against damage from water entry by two 

mechanical seals. The lower seal is 2-piece, silicon carbide/silicon 

carbide and the upper seal is unitized graphite impregnated 

silicon carbide.
The impeller and volute are designed for efficient flow 

characteristics and clog-free operation. The hardened cutters 

grind solids and fibrous matter into small particles that can be 

safely pumped through small diameter piping.

Pump System Components

 Control Panel

Float switches must be connected to an intrinsically safe 

circuit in the control panel as per the requirements of 

Chapter 5 of the National Electric Code®.

XLSG/XLSGX-Series grinder pumps require a separate, approved 

control panel for automatic operation. Operation will be 

according to the control selected. Refer to separate 

manufacturer’s instructions supplied with the unit.
The control panel shall be installed outside the hazardous area 

and appropriately isolated and sealed to prevent any potential 

ignition or explosion. Only approved controls that have 

intrinsically safe float switch connections shall be used. Mounting, 

installation and wiring connections are specific to the control 

panel used. Refer to the manufacturer’s instructions supplied with 

the unit. 

IMPORTANT: 

When connecting an XLSG/XLSGX-Series pump to 

an existing control panel, verify the panel is correctly sized and 

equipped for the pump.
The control panel for 3-phase pumps shall have provisions for the 

thermostats that open the motor contactors in order to maintain 

the T4 (135°C) temperature class. Do not exceed voltage/current 

combinations for the thermostat: 16 VDC/20 Amps, 115 VAC/

22 Amps, 277 VAC/8 Amps, 600 VAC/4 Amps. All models have a 

temperature (T) class rating of T4 with thermostats connected. 

Failure to use the proper circuitry and to connect the thermostat 

will void the T4 temperature class of the pump and will drop the 

temperature class to T3 (200°C).
Intrinsically safe control panels designed for use with the XLSG/

XLSGX-Series pumps available from Liberty Pumps can be found 

at http://www.LibertyPumps.com/Portals/0/Files/

panel_selection_guide.pdf or contact Liberty Pumps.
1-phase pumps require a panel-mounted start circuit consisting of 

a start capacitor, run capacitor, and start relay, which are available 

separately. Refer to Table 1 for these control panel components.

 Overload Protection

XLSG/XLSGX-Series grinder pumps require overload protection in 

the control panel. The motor control unit shall be approved and 

shall be properly sized or adjusted for the full load input power 

indicated on the pump nameplate. It is important to properly 

adjust or select the motor control overload protection. The full 

load amps on the nameplate should be used as a baseline, but it is 

important to consider that events such as supply voltage variation 

or large solids passing through the pump can temporarily increase 

current draw. To avoid possible nuisance tripping, it may be 

necessary to adjust overloads to a value slightly higher than the 

full load input power indicated on the pump nameplate.

 Thermostats

XLSG/XLSGX-Series grinder pumps are protected from 

overheating by means of thermal switches (thermostat) located in 

the motors. For 1-phase models, a hermetically sealed thermal 

overload device is mounted on the motor windings and wired 

directly in series with the motor’s winding, interrupting power in a 

high heat condition. 3-phase models utilize two thermostats 

mounted in series directly on the motor windings. The thermostat 

circuit shall be connected to a control panel that will stop power 

to the pump in a high temperature condition.
Both 1- and 3-phase pumps are constructed with class F materials, 

with a maximum operation temperature of 155°C. 

Failure to use 

the proper circuitry and connection of the thermostat will drop 

temperature class from T4 to T3 on 3-phase units

.

Many panels have a manual reset button for the thermostats on 

3-phase units. This button must be pressed to reset the system 

after the pump has cooled. 1-phase units reset automatically after 

the pump has cooled.

RISK OF SERIOUS INJURY OR DEATH

Table 1. Control Panel Components 1-Phase 

Required Component and Specification

Liberty Pumps

P/N

208 V 1-phase Start Kit

(contains 3 items listed separately below)

K001640

Start Capacitor, 270–324 µF 220/250 VAC

Run Capacitor, 65 µF 370 VAC

Start Relay

230 V 1-phase Start Kit

(contains 3 items listed separately below)

K001641

Start Capacitor, 270–324 µF 220/250 VAC

Run Capacitor, 50 µF 370 VAC

Start Relay

Содержание Omnivore XLSG200 Series

Страница 1: ...eference For replacement manual visit LibertyPumps com or contact Liberty Pumps at 1 800 543 2550 Retain dated sales receipt for warranty Model 7000 Apple Tree Avenue Bergen NY 14416 ph 1 800 543 2550...

Страница 2: ...y live wires inside the power cord The electrical power supply shall be located within the length limitations of the pump power cord and for below grade installations it shall be at least 4 ft 1 22 m...

Страница 3: ...rical terminations shall be made according to Federal State and Local codes for hazardous or classified locations Conduit junction boxes and associated components shall be approved for use with hazard...

Страница 4: ...the pump station is not complete If storage is necessary the pump should remain in its shipping container It should be stored in a warehouse or storage shed that has a clean dry temperature stable en...

Страница 5: ...SGX Series pumps available from Liberty Pumps can be found at http www LibertyPumps com Portals 0 Files panel_selection_guide pdf or contact Liberty Pumps 1 phase pumps require a panel mounted start c...

Страница 6: ...el or for a replacement relay refer to Table 2 Power and Control Cords Do not remove cord and strain relief and do not connect conduit to pump The power and control cords cannot be spliced a junction...

Страница 7: ...his distance must be determined by the engineer depending on the conditions of the application Cutter and Impeller Free Movement Check Wear Personal Protective Equipment to protect hands as cutter bla...

Страница 8: ...peration making sure all gaskets and components are present Use of a guide rail system shall be of a non sparking design Contact Liberty Pumps for available models such as GR20NS If guide rails are no...

Страница 9: ...dry basin should have impellers and cutters manually operated through the breaker panel monthly to lubricate the seals Pumps that are idle in a wet basin must be removed Quarterly 1 Check pumps for co...

Страница 10: ...p Unintentional ground Turn off power and check motor leads for possible ground 3 phase motor winding failure Check resistance of motor windings All three phases should have the same reading Obstructe...

Страница 11: ...proper capacity Discharge valve s partially closed or clogged Check the discharge line for foreign material including ice if the discharge line passes through or into cold areas Check valve partially...

Страница 12: ...or expenses resulting from installation or use of its products or for indirect incidental and consequential damages including costs of removal reinstallation or transportation There is no other expre...

Отзывы: