Check 3-phase pumps for correct rotation prior to installing 

pump(s) in basin. To change rotation, reverse any two of the 

three power leads to the pump (not the ground). Code the 

wires for reconnection after installation. 

Do not dispose of materials such as paint thinner or other 

chemicals down drains. Doing so could chemically attack and 

damage pump system components and cause product 

malfunction or failure.

Do not use pump system with mud, sand, cement, 

hydrocarbons, grease, or chemicals. Pump and system 

components can be damaged from these items causing 

product malfunction or failure. Additionally, flooding can 

occur if these items jam the impeller or piping.

Do not run dry.

Do not position the pump float directly under the inlet from 

drain tile or in the direct path of any incoming water.

Do not use pumps with fluid over 104°F (40°C). Operating the 

pump in fluid above this temperature can overheat the pump, 

resulting in pump failure.

The Uniform Plumbing Code® states that sewage systems 

shall have an audio and visual alarm that signals a 

malfunction of the system, to reduce the potential for 

property damage.

Keep pump upright.

At no time shall the pump be stored within an incomplete wet 

pit. The pump shall not be placed into the pit until it can be 

fully operational.

Do not allow the pump to freeze.

Model Specifications

For complete listing of models and their specifications, refer to 

http://www.LibertyPumps.com/About/Engineering-Specs. Pump 

nameplate provides a record of specific pump information.

Inspection and Storage

 Initial Inspection

The pump should be immediately inspected for damage that may 

have occurred in shipment.

1.

Visually check the pump and any spare parts for damage.

2.

Check for damaged electrical wires, especially where they exit 

the motor housing. 

Contact Liberty Pumps customer service to report any damage or 

shortage of parts.

 Storage Before Use

 

Protect the power and control cords from the environment. 

Unprotected power and control (switch) cords can allow 

water to wick through ends into pump or switch housings, 

causing surroundings to become energized.

 

At no time shall the pump be stored within an incomplete wet 

pit. The pump should not be placed into the pit until it can be 

fully operational.

Do not allow the pump to freeze.

XLSG/XLSGX-Series Omnivore grinder pumps are shipped from 

the factory ready for installation and use. The pump should be 

held in storage if the pump station is not complete.
If storage is necessary, the pump should remain in its shipping 

container. It should be stored in a warehouse or storage shed that 

has a clean, dry temperature-stable environment where the pump 

and its container are covered to protect it from water, dirt, 

vibration, etc. The cord ends must be protected against moisture. 

General Information

Before installation, read these instructions carefully. 

Each pump is individually factory tested to ensure 

proper performance. Closely following these 

instructions will eliminate potential operating 

problems, assuring years of trouble-free service.
The XLSG/XLSGX-Series pumps are to be used for 

handling septic tank effluent, sewage, and drain 

(storm) water.
Provide pump serial number in all correspondence.
Pumps are certified by CSA Group to CSA®, UL®, 

and FM standards for use in hazardous locations 

with division classification of Class 1, Division 1, 

Groups C and D; or as zone classified Class 1, 

Zone 1, and Groups IIA and IIB.
Pumps must be serviced at a qualified hazardous 

motor enclosure repair facility approved by Liberty 

Pumps. Any unauthorized field repairs void 

warranty and hazardous location ratings. Contact 

Liberty Pumps at 1-800-543-2550 to locate the 

closest authorized repair facility.

Operating Constraints

It is extremely important to verify that the pump 

has been sized correctly for the intended 

installation. The operating point of the pump must 

lie within the acceptable range as outlined by the 

applicable Liberty Pumps performance chart. 

Operating the pump outside of the recommended 

range can invalidate the CSA Certification of the 

pump and can also cause damage and premature 

failure. Operating outside of the recommended 

range can cause the pump to exceed its rated 

nameplate amp draw, which will void the pump 

certification. It can also cause motor overheating, 

cavitation, excessive vibration, clogging, and poor 

energy efficiency.

RISK OF ELECTRIC SHOCK

Содержание Omnivore XLSG Series

Страница 1: ...placement manual visit LibertyPumps com or contact Liberty Pumps at 800 543 2550 Retain dated sales receipt for warranty Model 7000 Apple Tree Avenue Bergen NY 14416 ph 800 543 2550 fax 585 494 1839 w...

Страница 2: ...by its power cord This will damage the power cord and could expose the electrically live wires inside the power cord The electrical power supply shall be located within the length limitations of the p...

Страница 3: ...motor enclosures Refer to Chapter 5 of the National Electric Code or applicable local codes and ordinances for all electrical and wiring requirements in hazardous locations Float switches must be conn...

Страница 4: ...sings causing surroundings to become energized At no time shall the pump be stored within an incomplete wet pit The pump should not be placed into the pit until it can be fully operational Do not allo...

Страница 5: ...void the T4 temperature class of the pump and will drop the temperature class to T3 200 C Intrinsically safe control panels designed for use with the XLSG XLSGX Series pumps available from Liberty Pum...

Страница 6: ...cords cannot be spliced a junction box may be used providing it is rated for hazardous locations and has approved cord connectors IMPORTANT Each cord has a green lead This is the ground wire and must...

Страница 7: ...he cutter Besides verification that the cutter and impeller are freely spinning rotating the cutter helps to lubricate the shaft seals if the pump has been non operational for more than a week It is r...

Страница 8: ...ected serious damage injury or death can result when power is applied Starting System 1 Verify all plumbing components in the basin are installed correctly and functional Verify all valves are open an...

Страница 9: ...ds warranty Table 2 Troubleshooting Matrix Problem Possible Cause Corrective Action Pump does not start Damaged power cable Return pump to an authorized repair facility Control panel selector switch i...

Страница 10: ...scharge line is blocked or restricted Check the discharge line for foreign material including ice if the discharge line passes through or into cold areas Check valve is stuck closed or installed backw...

Страница 11: ...cation Pump is being run below minimum head requirement causing cavitation A different sized pump or impeller may be required Consult Liberty Pumps Foreign objects in the impeller cavity Clean the imp...

Страница 12: ...operated or maintained per manufacturer instructions if it has been disassembled modified abused or tampered with if the electrical cord has been cut damaged or spliced if the pump discharge has been...

Отзывы: