Liberty Pumps LGH Series Скачать руководство пользователя страница 6

6 | EN

Copyright © Liberty Pumps, Inc. 2022 All rights reserved.

7550000G

 Overload Protection

LEP-Series pumps require overload protection in the control 

panel. The motor control unit shall be approved and shall be 

properly sized or adjusted for the full load input power indicated 

on the pump nameplate. It is important to properly adjust or 

select the motor control overload protection. The full load 

amperes on the nameplate should be used as a baseline, but it is 

important to consider that events such as supply voltage variation 

or large solids passing through the pump can temporarily increase 

current draw. To avoid possible nuisance tripping, it may be 

necessary to adjust overloads to a value slightly higher than the 

full load input power indicated on the pump nameplate.

 Power and Control Cords

Do not remove cord and strain relief, and do not connect 

conduit to pump.

The power and control cords are available either permanently 

potted into the cord cap or field-replaceable Quick-connect cords. 

For either option, the cords shall not be spliced.

IMPORTANT: 

Each cord has a green lead. This is the ground wire 

and shall be grounded properly per NEC and/or local codes.

 Seal Failure Probes

Dual seal LEP-Series pumps have a leak detection device mounted 

in an oil-filled cavity located between the two mechanical shaft 

seals. The device consists of two probes with a 200k

 

Ω resistor 

mounted between them. The circuit can be tested by checking for 

continuity between the seal leak wires; refer to the applicable 

wiring diagram. If the lower (outer) shaft seal begins to leak and 

water migrates into the cavity, it will be detected. Once a shaft seal 

failure is detected, the pump will continue to operate but service 

should be scheduled as soon as possible.
The LEP-Series control panels by Liberty Pumps have a seal leak 

detection system with a test button that monitors the integrity of 

the seal leak circuit and components. When pressed, the light 

should illuminate. The light should go off when the test button is 

released. If it remains on, the potentiometer is set too high. If the 

light does not illuminate, the light is burned out, the circuity is 

open, or the system does not have power. The seal leak relay 

requires adjustment upon installation. See 

Seal leak relay setup

 

on page

 

10.

Seal fail probes connect to a relay in the control panel, which is 

included in a Liberty Pumps control panel. For a non-Liberty 

Pumps control panel or for a replacement relay, refer to Table

 

2.

Wiring  Instructions

Always disconnect pump(s) from power source(s) before 

handling or making any adjustments to either the pump(s), 

the pump system, or the control panel.

All installation and maintenance of pumps, controls, 

protection devices, and general wiring shall be done by 

qualified personnel.

All electrical and safety practices shall be in accordance with 

the National Electrical Code

®

, the Occupational Safety and 

Health Administration, or applicable local codes and 

ordinances.

 Permanent Cord 1-Phase Wiring

 Pumps manufactured prior to 03/01/2021 

RISK OF ELECTRIC SHOCK

Table 2. Seal Fail Replacement Relay

Description

Relay 

Input 

Voltage

Liberty 

Pumps

P/N

Macromatic

P/N

Simplex, controls 1 pump

120V

K001672 SFP120A250

Duplex, controls 2 pumps

120V

K001675 SFP120C250

RISK OF ELECTRIC SHOCK

1

2 3

4

START SWITCH, SINPAC

CONTACTOR

START 

CAPS

RUN CAP

15K

2.2K

LINE

MOTOR

SEAL 
LEAK

POWER
CORD

CONTROL
CABLE

WHITE

WHITE

GREEN

ORANGE

ORANGE

RED

RED

WHITE

WHITE

BL

UE

WHITE

GREEN

GREEN

BL

A

CK

BL

A

CK

POTTING RESIN

THERMOSTAT

THERMOSTAT

SEAL FAILURE 

PROBES

GRAY

GRAY

Содержание LGH Series

Страница 1: ... system pressures Installer manual must remain with owner or system operator maintainer Record information from pump nameplate Model Serial Control Panel Mfg Date Install Date Dealer Dealer Ph 7000 Apple Tree Avenue Bergen NY 14416 ph 1 800 543 2550 fax 1 585 494 1839 www LibertyPumps com LEP 60 Hz 7550000G LGV Series LGH Series Ordinary Location Models XLGV Series XLGH Series Approved for Hazardo...

Страница 2: ...wer cord and could expose the electrically live wires inside the power cord The electrical power supply shall be located within the length limitations of the pump power cord and for below grade installations it shall be at least 4 ft 1 22 m above floor level Do not use this product in applications where human contact with the pumped fluid is common such as swimming pools fountains marine areas etc...

Страница 3: ... careful around pump base while power is connected Make sure that the pump is either in the tank or clear from people and wires when in operation Wear adequate Personal Protective Equipment when working on pumps or piping that have been exposed to wastewater Sump and sewage pumps often handle materials that can transmit illness or disease upon contact with skin and other tissues Do not enter a pum...

Страница 4: ...t trim impellers without consulting the factory Model Specifications For complete listing of models and their specifications refer to www LibertyPumps com lep About Engineering Specs Pump nameplate provides a record of specific pump information Inspection and Storage Initial Inspection The pump should be immediately inspected for damage that may have occurred in shipment 1 Visually check the pump ...

Страница 5: ...onents can be purchased separately using the part numbers shown Other options such as pre wired kits are also available Control Panels in Hazardous Locations Float switches must be connected to an intrinsically safe circuit in the control panel as per the requirements of Chapter 5 of the National Electric Code For hazardous locations the control panel must be installed outside the hazardous area a...

Страница 6: ... the pump will continue to operate but service should be scheduled as soon as possible The LEP Series control panels by Liberty Pumps have a seal leak detection system with a test button that monitors the integrity of the seal leak circuit and components When pressed the light should illuminate The light should go off when the test button is released If it remains on the potentiometer is set too h...

Страница 7: ...K POTTING RESIN RED WHITE ORANGE RUN CAP 80 MFD 370 VAC START CAP 270 324 MFD 330 VAC SEAL LEAK POWER CORD CONTROL CABLE ORANGE RED RED WHITE WHITE GREEN GREEN BLACK BLACK THERMOSTAT M3 M2 M1 L3 L2 L1 MOTOR GRAY BROWN BROWN GREEN GRAY THERMOSTAT SEAL FAILURE PROBES POTTING RESIN FOR HAZLOC PUMPS M3 M2 M1 1 6 7 2 4 8 3 5 9 200 230V 3PH 2D 460V 3PH 1D 15HP MODELS ONLY M3 M2 M1 1 1 2 2 3 1 2 3 3 7 7 ...

Страница 8: ...e 1 and Figure 2 Figure 1 Cut off Point 3 7 hp Pumps Figure 2 Cut off Point 10 15 hp Pumps Cutter and Impeller Free Movement Check Wear Personal Protective Equipment to protect hands as cutter blades have extremely sharp edges and present a serious cutting hazard Do not connect any power to pump until this check is complete Manually rotate the cutter and impeller to check that they spin freely wit...

Страница 9: ... as short as possible with a minimum number of turns to minimize friction head loss Do not reduce the discharge to below the pump outlet size Larger pipe sizes may be required to eliminate friction head loss over long runs Contact Liberty Pumps or other qualified person if questions arise regarding proper pipe size and flow rates Pressure Sewer Applications A redundant check valve assembly consist...

Страница 10: ...le of operation 7 Turn H O A switch es to OFF position and allow basin to fill to the override alarm control level s 8 Observe all floats in operation to verify that there is adequate clearance to the surrounds to ensure that the floats do not have the opportunity to get hung up in their travel 9 Verify alarm system response 10 Turn switch es to AUTO position pumps should start and operate togethe...

Страница 11: ...ps The only allowable repairs replacements without compromising the hazardous location rating of the pump are Quick connect cords lower outer shaft seals volute and impeller components Otherwise the pump must be returned to Liberty Pumps or an authorized hazardous repair facility for electrical and motor service This will ensure the integrity of the hazardous location rating of the pump and comply...

Страница 12: ...ctive float switch Replace float switch Missing or faulty curb stop swing check valve allowing system pressure to feed back through discharge piping Verify presence of a curb stop check valve or replace curb stop swing check valve assembly Pump operates with selector switch in Hand position but does not operate in Auto position Control circuits malfunctioning Check float switch level control or al...

Страница 13: ...essure to feed back through discharge piping Verify presence of a curb stop check valve or replace curb stop swing check valve assembly Pump runs periodically when fixtures are not in use Check valve not installed stuck open or leaking Install check valve s remove check valve and examine for freedom of operation and proper installation Fixtures are leaking Repair fixtures as required to eliminate ...

Страница 14: ... gravel or other abrasives if the product has been used to pump chemicals or hydrocarbons if the product has been moved from its original installation location or if the label bearing the serial and code number has been removed Liberty Pumps Inc shall not be liable for any loss damage or expenses resulting from installation or use of its products or for consequential damages including field labor ...

Отзывы: