Fusion SingleStar Installation Procedures
6.4.1
Installing a Fusion SingleStar Hub
CAUTION:
Install Fusion SingleStar Hubs in indoor locations
only.
Installing a Fusion SingleStar Hub in a Rack
The Fusion SingleStar Hub (3U high) mounts in a standard 19 in. (483 mm) equip-
ment rack. Allow clearance of 76 mm (3 in.) front and rear, and 51 mm (2 in.) on both
sides for air circulation. No top or bottom clearance is required.
Consideration:
• The Fusion SingleStar Hub is shipped with #10-32 mounting screws. Another
common rack thread is #12-24. Confirm that the mounting screws match the rack’s
threads.
To install the Hub in a rack:
1.
Insert spring nuts into rack where needed or use existing threaded holes.
2.
Place the Hub into the rack from the front.
3.
Align the flange holes with the spring nuts installed in Step 1.
4.
Insert the mounting screws in the appropriate positions in the rack.
5.
Tighten the mounting screws.