16
Fan Coil Unit
Installation
The power cord
connected to the unit should be
complied with the following specifications (Rubber
insulation, type H05RN-F approved by HAR or SAA).
If the supply cord is damaged, it must be replaced by a special cord or assembly availible from the manufacturer of its service agent.
Install Power Cord
CAUTION
20mm
GN/YL
NORMAL CROSS-SECTIONAL
AREA 1.25mm
2
Less thean 10mm
Less thean 10mm
T/B Cover
CAUTION:
Make sure that the screws of the terminal fixed tightly.
CAUTION:
Prepare the wiring as follows:
1) Never fail to have an individual power specialized for the unit. As for the method of wiring, be guided by the
circuit diagram pasted on the side panel.
2) Provide a circuit breaker switch between power source and the unit.
3) The screw which fasten the wiring in the casing of electrical fittings are liable to come loose from vibrations to
which the unit is subjected during the course of transportation. Check them and make sure that they are all
tightly fastened. (If they are loose, it could give rise to burn-out of the wires.)
4) Specification of power source
5) Confirm that electrical capacity is sufficient.
6) Be sure that the starting voltage is maintained at more than 90 percent of the rated voltage marked on the name
plate.
7) Confirm that the cable thickness is as specified in the power sources specification.
(Particularly note the relation between cable length and thickness.)
8) Never fail to equip a leakage breaker where it is wet or moist.
9) The following troubles would be caused by voltage drop-down.
• Vibration of a magnetic switch, damage on the contact point there of, fuse breaking, disturbance to the normal
function of a overload protection device.