background image

9

EN

 

Leak detection fluids are suitable for use with most refrigerants but the use of detergents containing 

chlorine shall be avoided as the chlorine may react with the refrigerant and corrode the copper pipe-

work.

 

If a leak is suspected, all naked flames shall be removed/extinguished. If a leakage of refrigerant is 

found which requires brazing, all of the refrigerant shall be recovered from the system, or isolated (by 

means of shut off valves) in a part of the system remote from the leak. Oxygen free nitrogen (OFN) shall 

then be purged through the system both before and during the brazing process.

Removal and evacuation

 

When breaking into the refrigerant circuit to make repairs – or for any other purpose – conventional 

procedures shall be used. However, it is important that best practice is followed since flammability is a 

consideration. The following procedure shall be adhered to:

 

Remove refrigerant

 

Purge the circuit with inert gas

 

Evacuate

 

Purge again with inert gas

 

Open the circuit by cutting or brazing.

 

The refrigerant charge shall be recovered into the correct recovery cylinders. The system shall be 

“flushed” with OFN to render the unit safe. This process may need to be repeated several times. 

Compressed air or oxygen shall not be used for this task.  Flushing shall be achieved by breaking 

the vacuum in the system with OFN and continuing to fill until the working pressure is achieved, then 

venting to atmosphere, and finally pulling down to a vacuum. This process shall be repeated until no 

refrigerant is within the system. When the final OFN charge is used, the system shall be vented down 

to atmospheric pressure to enable work to take place. This operation is absolutely vital if brazing 

operations on the pipe-work are to take place. Ensure that the outlet for the vacuum pump is not close to 

any ignition sources and there is ventilation available.

Charging procedures 

 

In addition to conventional charging procedures, the following requirements shall be followed.

 

Ensure that contamination of different refrigerants does not occur when using charging equipment. 

Hoses or lines shall be as short as possible to minimise the amount of refrigerant contained in them.

 

Cylinders shall be kept upright.

 

Ensure that the refrigeration system is earthed prior to charging the system with refrigerant.

 

Label the system when charging is complete (if not already).

 

Extreme care shall be taken not to overfill the refrigeration system. Prior to recharging the system it 

shall be pressure tested with OFN. The system shall be leak tested on completion of charging but prior 

to commissioning. A follow up leak test shall be carried out prior to leaving the site.

Decommissioning

 

Before carrying out this procedure, it is essential that the technician is completely familiar with the 

equipment and all its detail. It is recommended good practice that all refrigerants are recovered safely. 

Prior to the task being carried out, an oil and refrigerant sample shall be taken in case analysis is 

required prior to re-use of reclaimed refrigerant. It is essential that electrical power is available before the 

task is commenced. 

a) Become familiar with the equipment and its operation. 

b) Isolate system electrically.

c) Before attempting the procedure ensure that: 

• mechanical handling equipment is available, if required, for handling refrigerant cylinders; 

• all personal protective equipment is available and being used correctly; 

• the recovery process is supervised at all times by a competent person; 

• recovery equipment and cylinders conform to the appropriate standards. 

d) Pump down refrigerant system, if possible. 

e) If a vacuum is not possible, make a manifold so that refrigerant can be removed from various parts of 

the system. 

f) Make sure that cylinder is situated on the scales before recovery takes place. 

g) Start the recovery machine and operate in accordance with manufacturer’s instructions. 

h) Do not overfill cylinders. (No more than 80 % volume liquid charge).

i) Do not exceed the maximum working pressure of the cylinder, even temporarily. 

Содержание W121CE

Страница 1: ...2022 LG Electronics Inc All Rights Reserved MFL71860124 Rev 00_022122 AIR CONDITIONER Read this owner s manual thoroughly before operating the appliance and keep it handy for reference at all times OWNER S MANUAL TYPE WINDOW W121CE SL0 W122CE SL0 ...

Страница 2: ...eeded 13 How to Install the Unit 14 Preparation of the Cabinet 14 Drainage Optional 14 Installation of the Cabinet 15 Space for Outside Air Flow 15 Installations of the unit into the Cabinet 16 OPERATION 17 Control Panel and Remote Control 17 Wireless Remote Control 18 Air Direction 19 Slinger Fan 19 MAINTENANCE 20 Air Filter 20 TROUBLESHOOTING 21 Before Calling for Service 21 Normal Sounds You Ma...

Страница 3: ...ay be injured or cause damage to the product if you do not follow instructions All safety messages will tell you what the potential hazard is tell you how to reduce the chance of injury and tell you what may happen if the instructions are not followed The following symbols are displayed on units This symbol indicates that this appliance uses a flammable refrigerant If the refrigerant is leaked and...

Страница 4: ...circumstances cut or remove the third ground prong from the power cord When installing or moving the appliance be careful not to pinch crush or damage the power cord Plug in the power plug properly Do not modify or extend the power cord Do not start stop operation by plugging unplugging the power cord Do not turn on the circuit breaker or power under condition that front grille cabinet control box...

Страница 5: ... capabilities or lack of experience and knowledge unless they have been given supervision or instruction concerning the use of the appliance by a person responsible for their safety Children should be supervised to ensure that they do not play with the appliance The interior of the product must only be cleaned by an authorized service center or a dealer Do not use solvent based detergent on the pr...

Страница 6: ...g the appliance be careful not to pinch crush or damage the power cord Make sure the air inlet and outlet are free from obstructions Use a soft cloth to clean the appliance Do not use waxes thinners or harsh detergents Do not step on or place heavy objects on top of the appliance Do not operate the appliance without the filter securely installed Do not drink water drained from the appliance Be sur...

Страница 7: ...rk that contains or has contained flammable refrigerant shall use any sources of ignition in such a manner that it may lead to the risk of fire or explosion All possible ignition sources including cigarette smoking should be kept sufficiently far away from the site of installation repairing removing and disposal during which flammable refrigerant can possibly be released to the surrounding space P...

Страница 8: ...damage to seals incorrect fitting of glands etc Ensure that apparatus is mounted securely Ensure that seals or sealing materials have not degraded such that they no longer serve the purpose of preventing the ingress of flammable atmospheres Replacement parts shall be in accordance with the manufacturer s specifications Repair to intrinsically safe components Do not apply any permanent inductive or...

Страница 9: ...al charging procedures the following requirements shall be followed Ensure that contamination of different refrigerants does not occur when using charging equipment Hoses or lines shall be as short as possible to minimise the amount of refrigerant contained in them Cylinders shall be kept upright Ensure that the refrigeration system is earthed prior to charging the system with refrigerant Label th...

Страница 10: ...in good working order Empty recovery cylinders are evacuated and if possible cooled before recovery occurs The recovery equipment shall be in good working order with a set of instructions concerning the equipment that is at hand and shall be suitable for the recovery of flammable refrigerants In addition a set of calibrated weighing scales shall be available and in good working order Hoses shall b...

Страница 11: ...onds to the room area as specified for operation The appliance shall be stored so as to prevent mechanical damage from occurring Technical Safety Any person who is involved with working on or breaking into a refrigerant circuit should hold a current valid certificate from an industry accredited assessment authority which authorises their competence to handle refrigerants safely in accordance with ...

Страница 12: ... 7 3 4 5 6 7 1 2 1 Control Panel 1 Evaporator 2 Remote Control 2 Air Guide 3 Air Filter 3 Brace 4 Vertical Air Deflector Horizontal Louver 4 Compressor 5 Horizontal Air Deflector Vertical Louver 5 Condenser 6 Front Grille 6 Base Pan 7 Air Outlet 7 Power Cord 8 Cabinet ...

Страница 13: ...it Breaker Circuit Breaker Use a circuit breaker or time Use a circuit breaker or time delay fuse delay fuse NOTE Model Voltage Frequency Circuit Breaker W121CE SL0 115 V 60 Hz 20 A W122CE SL0 220 V 60 Hz 15 A Installation Overview Screw Screw For Front Grille L 10mm 2EA For Front Grille L 10mm 2EA Foam Foam L 30mm 3EA L 30mm 3EA Drain pan Drain pan Tools Needed Phillips head screwdriver Flat blad...

Страница 14: ...move 4 screws which fasten the cabinet at both sides and at the back Keep the screws for later use Shipping Shipping Screws Screws 2 Slide the unit from the cabinet by gripping the base pan handle and pulling forward while bracing the cabinet CAUTION The unit is heavy To prevent injury use proper lifting techniques when pulling unit forward from cabinet Obtain assistance from another person if pos...

Страница 15: ... appearance and protection against the weather insects and rodents NOTE Unit may be supported by a solid frame from below or by a hanger from a solid overhead support FLASH OR SEAL AROUND EXTERNAL WALL FRAME OR ARCHITRAVE STURDY TIMBER FRAME ALL ROUND UNIT DRAIN CHUTE EXTERNAL SUPPORT FRAME AT BALANCE POINT OF RAC Preferred method of installation into a timber framed wall partition or window ALTER...

Страница 16: ...ury 2 Stuff the foam around the unit to prevent air and insects from getting into the room The Foam The Foam Around the unit Around the unit 3 Connect the wire harness from the front grille assembly to the air conditioner 4 Attach the front grille assembly to the cabinet by inserting the grille tabs into the slots on the front of the cabinet Push the grille in until it snaps into place 5 Remove ai...

Страница 17: ...nnot adjust the set temperature Dry Deshum This mode is ideal for rainy and damp days to dehumidify the room rather than cooling it significantly Humidity is removed from the room by the combination of compressor operation and the fan speed fixed at Low The compressor and fan turn off once the set temperature is reached Fan speed cannot be adjusted in Dry Deshum mode 2 Fan Speed Press to set the F...

Страница 18: ...nergy Saver Ahorro Energía The unit defaults to the Energy Saver Ahorro Energía mode each time the unit is switched on except in Fan Vent mode or when power is restored after an electrical power outage The remote control will not function properly if the AC infrared sensor is exposed to direct light or if there are obstacles between the remote controller and the air conditioner Wireless Remote Con...

Страница 19: ...ection Touch the horizontal louvers to adjust the airflow up or down NOTE When the weather is extremely hot the unit may turn off automatically to protect the compressor Slinger Fan This air conditioner is equipped with a slinger fan See drawing The fan s outer ring picks up the condensed water from the base pan if the water level gets high enough The water is then picked up by the fan and expelle...

Страница 20: ...water below 40 C 104 F 3 Gently shake the excess water from the filter 4 Dry the filter in the shade 5 Insert the filter into the Front grille Cleaning the Air Conditioner Wipe the front grille and inlet grille with a cloth dampened in a mild detergent solution Wash the cabinet with mild soap or detergent and lukewarm water then polish using liquid appliance wax NOTE To ensure continued peak effic...

Страница 21: ...y s high efficiency compressors may have a high pitched chatter during the cooling cycle 2 Sound of Rushing Air At the front of the unit you may hear the sound of rushing air being moved by the fan 3 Gurgle Hiss Gurgling or hissing noise may be heard due to refrigerant passing through evaporator during normal operation 4 Vibration Unit may vibrate and make noise because of poor wall or window cons...

Страница 22: ... or furniture blocking the front of the air conditioner The temp control may not be set correctly Set the desired temperature to a level lower than the current temperature The air filter is dirty Clean the filter at least every 2 weeks See the MAINTENANCE Cleaning the Air Filter section The room may have been hot When the air conditioner is first turned on you need to allow time for the room to co...

Страница 23: ...ion instructions or check with installer Noise when unit is cooling Air movement sound This is normal If too loud set to lower FAN Speed Window vibration poor installation Refer to installation instructions or check with installer Room too cold Set temperature too low Increase set temperature Remote sensing deactivating prematurely Remote control not located within range Place remote control withi...

Страница 24: ...LG ELECTRONICS MEXICO S A DE C V Sor Juana Inés de la Cruz No 555 Col San Lorenzo Industrial Tlalnepantla de Baz Estado de México C P 54033 Tel 55 5321 1919 Página web http www lg com mx ...

Отзывы: