16
INSTALLATION OF OUTDOOR UNIT
ENGLISH
• Single Operation
1) Standard Inverter
2) Compact Inverter
If installed tube is shorter than 7.5 m,
additional charging is not necessary.
Additional Refrigerant
= [A-7.5 (m)] x Additional refrigerant (g/m)
The installation of pipe-work shall be kept
to a minimum.
Outdoor unit
Indoor unit
A
B
Outdoor unit
Indoor unit
A
B
Capacity
(kBtu/h)
Pipe Size mm(inch)
Length A(m)
Elevation B(m)
Additional
refrigerant
(g/m)
Gas
Liquid
Standard
Max.
Standard
Max.
9
Ø 9.52 (3/8)
Ø 6.35 (1/4)
7.5
20
5
15
20
12
Ø 9.52 (3/8)
Ø 6.35 (1/4)
7.5
20
5
15
20
18
Ø 12.7 (1/2)
Ø 6.35 (1/4)
7.5
30
5
30
20
24
Ø 15.88 (5/8)
Ø 9.52 (3/8)
7.5
50
5
30
35
30
Ø 15.88 (5/8)
Ø 9.52 (3/8)
7.5
50
5
30
40
36
Ø 15.88 (5/8)
Ø 9.52 (3/8)
7.5
85
5
30
40
42
Ø 15.88 (5/8)
Ø 9.52 (3/8)
7.5
85
5
30
40
48
Ø 15.88 (5/8)
Ø 9.52 (3/8)
7.5
85
5
30
40
60
Ø 15.88 (5/8)
Ø 9.52 (3/8)
7.5
85
5
30
40
Piping length and the elevation
Capacity
(kBtu/h)
Pipe Size mm(inch)
Length A(m)
Elevation B(m)
Additional
refrigerant
(g/m)
Gas
Liquid
Standard
Max.
Standard
Max.
18
Ø 12.7 (1/2)
Ø 6.35 (1/4)
7.5
30
5
30
20
24
Ø 15.88 (5/8)
Ø 9.52 (3/8)
7.5
35
5
30
35
30
Ø 15.88 (5/8)
Ø 9.52 (3/8)
7.5
35
5
30
35
36
Ø 15.88 (5/8)
Ø 9.52 (3/8)
7.5
50
5
30
40