FUNCTION
ENGLISH
43
PCB Display(18 k Model Only)
It is useful to check the cycle data without LGMV.
Whenever you push the Tact Switch, the cycle information will be shown as below.
h
After 1 page is displayed, subsequently 2 page is displayed.
Tact S/W
Item
Display
Example
1page
2page
1 time
Low Pressure
890 kpa
‘LP’
’89’
2 times
Hi Pressure
2 900 kpa
‘HP’
‘290’
3 times
Discharge Temp.
85 °C
‘DS’
’85’
4 times
Cond Out Temp.
-10 °C
‘CS’
‘-10’
5 times
Suction Temp.
-10 °C
‘SS’
‘-10’
6 times
ODU Air Temp.
-10 °C
‘AS’
‘-10’
7 times
Current
15 A
‘A’
‘15’
8 times
Voltage
230 V
‘V’
‘230’
9 times
Comp Hz
100 Hz
‘F’
‘100’
10 times
DC Link Voltage
230 V
‘dc’
‘230’
TACT-SW1
When you push the Tact Switch, use the material non-conducting electricity.
WARNING
!
Operating Method