How to Set E.S.P?
Installation Manual
25
ENGLISH
NOTE
1. Be sure to set the value refering table 1. Unexpected set value will cause mal-function.
2. Table 1 is based at 230 V. According to the fluctuation of voltage, air flow rate varies.
3. Factory Set(External Static Pressure) each Model
* If it is zero static pressure, please set value below Maximum value.
Model
Step
CMM
Static Pressure[mmAq(Pa)]
Setting Value
UB85W.N94R0
LOW
64
MID
72
HIGH
80
Model
Maximum value
UB85W.N94R0
UB70W.N94R0
105
Model
Factory set (E.S.P.) mmAq(Pa)
UB85W.N94R0
UB70W.N94R0
13 (127)
6(59)
7(69)
8(78)
9(88)
10(98) 12(118) 13(127) 14(137) 15(147) 16(157) 18(176)
32:01
32:02
32:03
32:04
32:05
32:06
32:07
32:08
32:09
32:10
32:11
74
75
76
78
79
82
84
86
89
91
95
78
79
80
82
83
87
89
91
94
96
100
82
84
86
88
90
93
95
97
100
101
105
Model
Step
CMM
Static Pressure[mmAq(Pa)]
Setting Value
UB70W.N94R0
LOW
60
MID
65
HIGH
70
6(59)
7(69)
8(78)
9(88)
10(98) 12(118) 13(127) 14(137) 15(147) 16(157) 18(176)
32:01
32:02
32:03
32:04
32:05
32:06
32:07
32:08
32:09
32:10
32:11
70
72
74
76
78
81
82
85
86
88
91
74
76
78
80
82
85
86
89
90
92
95
78
80
82
84
86
90
91
93
94
96
99