Error Codes.
36
Therma V R32 Installation Instructions.
First two weeks: Blocked filters and/or air pockets
Flow rate alarms are likely to occur during the first two weeks after commissioning; this is due to the formation of
air-pockets which may occur and temporarily affect the flow-rate. In most cases, the air will migrate to the auto-air
vents (AAV) and release without any requirement for intervention.
Equally, if any sediments are in the hydronic pipework, they will be caught by the internal strainer. Blockages in the
strainer can cause CH14 alarms. In this case, the strainers will need to be cleaned
Recommendation
: once the unit has been installed, advise the customers that it is quite likely and normal for a CH14 alarm
to occur in the first two weeks. This will give the customer reassurance if and when the fault does arise!
If the cause was air, then a simple power reset could allow the system to continue working as normal, once the pocket of air
has made its way to the AAV
CH14
TANK MODE ONLY
1.
Restriction in coil
HEAT MODE ONLY
1.
Restriction in Heating Circuit
2.
Excessive pressure drop
HEAT & TANK MODE
1. Low system water pressure
2. Strainers and Filters blocked
3. Water-pump fault
4. Flow Switch Abnormality
5. PCB Fault
Fault arises during:
Testing each mode separately can help you to deduce where the fault lies
:
Содержание Therma V R32
Страница 1: ...R32 Monobloc April 2020 Installation Instructions Therma V R32 Generation 3 ...
Страница 9: ...Installation Schematic 9 Therma V R32 Installation Instructions DHW Heating with 1 Zone 5 7 9kW ...
Страница 10: ...Installation Schematic 10 Therma V R32 Installation Instructions DHW Pre Plumb Heating with 1 Zone 5 7 9kW ...
Страница 11: ...Installation Schematic 11 Therma V R32 Installation Instructions DHW Heating with 1 Zone 12 14 16kW ...
Страница 12: ...Installation Schematic 12 Therma V R32 Installation Instructions DHW Pre Plumb Heating with 1 Zone 12 14 16kW ...
Страница 13: ...Installation Schematic 13 Therma V R32 Installation Instructions DHW Heating with 2 Zone s 5 7 9kW ...
Страница 14: ...Installation Schematic 14 Therma V R32 Installation Instructions DHW Pre Plumb Heating with 2 Zone s 5 7 9kW ...
Страница 15: ...Installation Schematic 15 Therma V R32 Installation Instructions DHW Heating with 2 Zone s 12 14 16kW ...
Страница 16: ...Installation Schematic 16 Therma V R32 Installation Instructions DHW Heating Rad s UFH 2 Zone 12 14 16kW ...
Страница 19: ...Installation Schematic 19 Therma V R32 Installation Instructions DHW Boiler with Two Heating Zone s 12 14 16kW ...
Страница 21: ...Installation Schematic 21 Therma V R32 Installation Instructions DHW with 2 Heat Pumps 12 14 16kW ...
Страница 22: ...Installation Wiring 22 Therma V R32 Installation Instructions DHW 2 Heat Pumps 12 14 16kW ...
Страница 26: ...26 Therma V R32 Installation Instructions Installation Wiring Relay Example ...
Страница 27: ...27 Therma V R32 Installation Instructions Installation Wiring Relay Example ...
Страница 31: ...Central Controller 31 Therma V R32 Installation Instructions ...
Страница 37: ...Configuration Installer Setting 37 Therma V R32 Installation Instructions ...
Страница 38: ...Configuration Installer Setting 38 Therma V R32 Installation Instructions Rads 50degC UFH 40degC ...
Страница 39: ...39 Therma V R32 Installation Instructions ...