Error Codes
Code No.
Description
Cause
Normal Condition
1
Problem in remote room air sensor
•
Incorrect connection between
sensor and PCB(Heater).
•
PCB(Heater) fault
•
Sensor fault
•
Resistance: 10 kO at 25 centigrade
(unplugged) -+ for Remote room air
sensor
•
Resistance: 5 kO at 25 centigrade
(unplugged)-+ for all sensors EXCEPT
remote room air sensor
•
Voltage: 2.5
V
DC at 25 centigrade
(plugged) (for all sensors)
•
Refer resistance-temperature table to
check in different temperature
2
Problem in refrigerant (inlet side) sensor
6
Problem in refrigerant (outlet side) sensor
8
Problem in
water
tank sensor
13
Problem in solar pipe sensor
16
Problems in sensors
17
Problem in
water-inlet
sensor
18
Problem in
water-outlet
sensor
19
Problem in electric heater outlet sensor
10
BLOC Water pump Lock
Restriction of BLOC Water pump
•
BLOC Water pump defect/
assembly condition abnormal
•
Fan lock by foreign material
3
Bad communication between remote
controller and unit.
•
Incorrect connection between
sensor and PCB(Heater)
•
PCB(Heater) fault
•
Sensor fault
•
Wire connection between remote
controller and Main PCB
assembly(Heater) should be tight
•
Output
voltage
of PCB should be 12 V
DC
5
Bad communication between Main PCB
assembly(Heater) and Main PCB assembly(lnverter)
of the unit.
•
The connector for transmission is
disconnected
•
The connecting
wires
are
misconnected
•
The communication line is broken
•
Main PCB assembly(lnverter) is
abnormal
•
Main PCB assembly(Heater) is
abnormal
•
Wire connection between remote
control panel and Main PCB
assembly(Heater) should be tight.
53
9
PCB program (EEPROM) fault
•
Electrical or mechanical damage a
the EEPROM
•
This error can not be permitted
14
Problem in flow switch
•
Flow switch is open
while
internal
water
pump is
working
•
Flow switch is closed
while
internal
water
pump is not
working
•
Flow switch is open
while
DIP
switch No. 5 of Main PCB
assembly(Heater) is set as on
•
Flow switch should be closed
while
internal
water
pump is
working
or DIP
switch No. 5 of Main PCB
assembly(Heater) is set as on
•
Flow switch should be open
while
internal
water
pump is not
working
15
Water pipe overheated
•
Abnormal operation of electric
heater
•
Leaving
water
temperature is
above 72
°C.
•
If there is no problem in electric heater
control, possible maximum leaving
water
temperature is 72
°C