Error Codes 

 

Code No. 

Description 

Cause 

Normal Condition 

1

 

Problem  in remote  room air  sensor

 

 
 
 

 

• 

Incorrect connection between 

sensor and PCB(Heater).

 

• 

PCB(Heater)  fault

 

• 

Sensor fault

 

• 

Resistance:  10 kO at 25 centigrade 

(unplugged)  -+ for  Remote  room air 

sensor

 

• 

Resistance:  5 kO at 25 centigrade 

(unplugged)-+ for all sensors EXCEPT 

remote room air sensor

 

• 

Voltage:  2.5 

DC at 25 centigrade 

(plugged)  (for all sensors)

 

• 

Refer resistance-temperature table to 

check in different temperature

 

2

 

Problem  in refrigerant  (inlet  side)  sensor

 

6

 

Problem  in refrigerant  (outlet  side)  sensor

 

8

 

Problem in 

water 

tank sensor

 

13

 

Problem in solar pipe  sensor

 

16 

Problems  in sensors

 

17

 

Problem  in 

water-inlet 

sensor

 

18

 

Problem in 

water-outlet 

sensor

 

19

 

Problem  in electric  heater  outlet  sensor

 

 

10

 

 

BLOC Water pump Lock

 

 

Restriction of BLOC Water pump

 

• 

BLOC Water pump defect/ 

assembly  condition  abnormal

 

• 

Fan lock by foreign material

 

 
 

 

3

 

 

 

Bad communication between remote 

controller and unit.

 

 

• 

Incorrect connection between 

sensor and PCB(Heater)

 

• 

PCB(Heater)  fault

 

• 

Sensor fault

 

• 

Wire connection between remote 

controller and Main PCB 

assembly(Heater) should  be  tight

 

• 

Output 

voltage 

of  PCB  should be 12 V 

DC

 

 
 
 

5

 

 
 
 

 

Bad communication between Main PCB 

assembly(Heater) and Main PCB assembly(lnverter) 

of the unit.

 

• 

The connector for transmission is 

disconnected

 

• 

The connecting 

wires 

are 

misconnected

 

• 

The  communication  line is broken

 

• 

Main PCB assembly(lnverter) is 

abnormal

 

• 

Main  PCB assembly(Heater) is

 

abnormal

 

 
 
 

 

• 

Wire connection between remote 

control panel and Main PCB 

assembly(Heater)  should  be  tight.

 

 

53

 

9

 

PCB program (EEPROM)  fault

 

• 

Electrical  or mechanical  damage a

 

the EEPROM

 

• 

This error  can not  be permitted

 

 
 
 

 

14

 

 
 
 

 

Problem in flow switch

 

• 

Flow switch is open 

while 

internal 

water 

pump is 

working

 

• 

Flow switch is closed 

while 

internal 

water 

pump is not 

working

 

• 

Flow switch is open 

while 

DIP

 

switch No. 5 of Main PCB 
assembly(Heater) is set as  on

 

• 

Flow switch should be closed 

while 

internal 

water 

pump is 

working 

or DIP 

switch No. 5 of Main  PCB 

assembly(Heater) is set as on

 

• 

Flow switch should be open 

while

 

internal 

water 

pump is not 

working

 

 

 

15 

 

 

Water  pipe overheated

 

• 

Abnormal operation of electric 

heater

 

• 

Leaving 

water 

temperature is

 

above 72 

°C.

 

• 

If there is no problem in electric heater 

control, possible maximum leaving 

water 

temperature  is 72 

°C

 

Содержание Therma V R32 Gen3

Страница 1: ...LG Therma V R32 Gen3 Typical Installation with Third Party controls Installation and Setup Monobloc system Rev 1 0 January 14th 2022 ...

Страница 2: ...set the room temperature at different times of the day The heat pump controls the domestic hot water temperature itself including for an optional sterilization cycle and is assisted by the immersion heater 2 port valves MUST not to be used upstream of the buffer The hot water control is managed through the LG controller Hot water takes priority over heating There is no electric heater inside the m...

Страница 3: ...t we would recommend no less than 2m Allowance for the condensate to soakaway via a soakaway of to drain not to allow ice formation around the unit Anti freeze is recommended to protect again frost damage this should be premixed and added to the system we will go into further detail later The water quality should be tested against LG Requirements The Mains power must be turned on 6 Hours before st...

Страница 4: ...y Power supplies sizes are All Electrical cable sizes should be checked on site by a NICEIC qualified electrician The Following Points must be followed o RCD Type C o Rotary Enclosed Isolation switch IP65 o Mandatory electricity meter fitted within an enclosed box o Ensure power cable does not touch refrigerant pipework ...

Страница 5: ...t page Connections are made to the directly to the Monoblock via the 1st wiring centre as shown below Wiring back to terminals differs on older models until August 2020 Third Party controls should be wired through terminal 17 L and terminal 20 L2 using a NO Relay Please see below schematic for single Zone operation through 3rd party controls this should be integrated with the above for DHW control...

Страница 6: ...firmed with the LG manual All Electrical work should be completed by NICEIC approved Electrician DIP Switch Settings The unit contains a number of DIP switches these must be set prior to powering up the unit in order to allow the unit to operate correctly and to allow some features to function The Dip Switches are laid out as the diagram below SW2 1 Off Master 2 Off 3 ON unit Outdoor Unit DHW tank...

Страница 7: ...rature setting but an offset that can be applied to the default value of 0 as shown in the previous slide When the function is activated the default value is 5 Example if setting 10 is used entering water temp for judgment is reduced from 15 to 5 for protection starting entering water for condition release is reduced from 18 15 3 to 8 5 3 Pre Start Check Please check the following prior to startin...

Страница 8: ...th OK 2 Use the Right hand button Select Setting Press and Hold the up Button for 3 Seconds 3 4 square boxes are shown enter the Password this is the software version in the right hand bottom corner of the screen You are now in the Installer Configuration menu The following setting need to be set for Basic operation Software Version ok ok Min Max 30 50 55 RADS 40 45 UFH ok ok ...

Страница 9: ...W www seconrenewables com T 0191 516 6554 E info seconrenewables com ok Use Sun 1 00am ok ok ok 60 30 Force end time 1 ok Main Booster Heater ON ok ok 60 0 60 ok ok AS ABOVE ok ...

Страница 10: ...8 C with a Design Flow temp of 50 C for Radiators Controler Video LG Therma V R32 Monobloc Installer Setting Guide Bing video Function Description Range Default Set Outdoor 1 Heat OUT 1 Heating Lower ambient Temp 25 35 c 10 c 2 8 c Outdoor 2 Heat OUT 2 Heating Higher ambient Temp 16 c 19 c Water1 Heat LW1 Heating higher Water Temp Dependant on Field Settings 35 c 50 c Water2 Heat LW2 Heating Lower...

Страница 11: ...u Select Pump test run To use this function the antifreeze short pin must be open and switch No 2 in Option SW 3must be on Please See Earlier Section Regards Antifreeze Levels Through out this process the Flowrate should be observed to check it meet MI The system should be vent of air and check that it is full of water ...

Страница 12: ...on the unit does not operated for the sake of system protection Wait while unit warms up to 18 C the water inlet temperature If you are not using the back up heater accessory HA 1M E1 increase the water temperature with theexternal heat source heater boiler If the problem persists contact your dealer If you want to use the screed drying function be sure to purchase and install back up hater access...

Страница 13: ...ter fault Sensor fault Wire connection between remote controller and Main PCB assembly Heater should be tight Output voltage of PCB should be12 V DC 5 Bad communication between Main PCB assembly Heater and Main PCB assembly lnverter of the unit The connector for transmission is disconnected The connecting wires are misconnected The communication line is broken Main PCB assembly lnverter is abnorma...

Страница 14: ... Connection Check Input Voltage Check PCB DC Link voltage sensor parts 24 Low High PressureSwitch Perception Error Low pressure is below 0 2 kgf cm2 High pressure is above 42 44kgf cm2 Pressure switch is self defective Check the low high pressure Check the connection of harness 26 DC CompressorPosition Compressor Starting fail error Check the connection of comp wire U V W Malfunction of compressor...

Страница 15: ...rmistor connector Open Short 3 Defect of outdoor PCB lnverter 46 Problem in suctionpipe temperature sensor Open Short Soldered poorly Internal circuit error 1 Bad connection of thermistor connector 2 Defect of thermistor connector Open Short 3 Defect of outdoor PCB lnverter 52 PCB CommunicationError Checking the communication state between Main PCB and Inverter PCB Generation of noise source inter...

Страница 16: ... EBR37798112 21 Check the soldered condition in the 22 23 pin of 1PM PFCM Check the screw torque of 1PM PFCM Check the spreadable condition of thermal grease on1PM PFCM Check the outdoor fan is driving rightly 65 Problem in HeatsinkTemperature sensor Abnormal value of sensor Open Short Check if there is defect of thermistor connector Open Short Check defect of outdoor PCB lnverter Display code Tit...

Страница 17: ...ment for intervention Equally if any sediments are in the hydronic pipework they will be caught by the internal strainer Blockages in thestrainer can cause CH14 alarms In this case the strainers will need to be cleaned Recommendation once the unit has been installed advise the customers that it is quite likely and normal for a CH14 alarmto occur in the first two weeks This will give the customer r...

Страница 18: ...6554 E info seconrenewables com Have you visited our web shop yet www seconrenewables com Secon Renewables Unit 87 Business Innovation Centre Wearfield Sunderland SR5 2TH T 0191 516 6554 E info seconrenewables com W www seconrenewables com ...