Additional gas charging
(Gas leakage)
ï When refrigerant is insufficient by leakage, recharge the unit with the refrigerant up to normal operating suc-
tion pressure.
ï Use the graph or the equation below to get operating suction pressure according to indoor and outdoor tem-
perature.
Suction pressure was measured at 3-way valve service port after operating the unit for 10 minutes.
The method of using graph
- Find outdoor temperature.
- Find indoor temperature onto the curve of outdoor temperature.
- Read suction pressure at the axis of ordinates.
The method of using equation
-. Calculate suction pressure after putting indoor and outdoor temperature into the equation.
13
(At operating the Unit for 10 minutes)
Suction Pressure
(Kg/cm
2
.g)
Outdoor Temp.
(∞
C)
Indoor Temp. (∞
C)
12
11
10
9
8
7
6
5
5
10
15
20
25
30
35
40
50∞
C
40∞
C
30∞
C
20∞
C
10∞
C
0∞
C
P = 3 + 0.0123 x T
out
1.5
+ 0.8 x T
in
0.5
Where, P
: Suction Pressure(kg/cm
2
.g)
Tout : Outdoor Temperature(∞
C)
Tin
: Indoor Temperature(∞
C)
Operating Suction Pressure (For R4
10
A)
(According to Indoor & Outdoor Temperature)
-36-
Содержание S4-S5-SE Chassis
Страница 1: ...MODELS S4 S5 SE Chassis ...
Страница 2: ...3 5 6 7 12 12 13 24 25 28 34 2 ...
Страница 3: ...IN DOOR Lights up during indoor unit operation Optional 3 ...
Страница 4: ... Optional 4 ...
Страница 6: ... 6 09K 12K 18K 24K ...
Страница 11: ... 11 ...
Страница 12: ... 12 ...
Страница 14: ... 14 More than 10cm More than 5cm More than 2 3m More than 5cm ...
Страница 17: ... 17 ...
Страница 18: ... 18 Drain hose Drain hose Connecting pipe Connecting cable Tape Drain hose Drain hose Connecting cable ...
Страница 19: ... 19 Piping for passage through piping hole Tubing holder ...
Страница 21: ... 21 Outdoor unit Gas side piping Bigger diameter Liquid side piping Smaller diameter Torque wrench ...
Страница 22: ... 22 ...
Страница 23: ... 23 Circuit Breaker A 15 Grade 9k 12k 20 18k 30 24k ...
Страница 24: ... 24 Pull the right and the left side ...
Страница 25: ... 25 Pull the right and the left side ...
Страница 26: ... 26 Discharge temperature Discharge air Intake temperature ...
Страница 27: ... 27 ...
Страница 28: ...Earth Conductor 28 ...
Страница 29: ...Screw 29 ...
Страница 30: ... 30 Motor cover Bearing Cross flow fan ...
Страница 31: ... 31 ...
Страница 37: ... 37 ...
Страница 38: ... 38 ...
Страница 39: ... 39 ...
Страница 40: ... 40 ...
Страница 41: ... 41 ...
Страница 42: ... 42 ...
Страница 43: ... 43 ...
Страница 44: ...P No 5400575301 ...