Setting and Using Method
Installation manual
21
• Demand control by analog input control (10 Step)
SW_ STEP
Normal
(V)
Input voltage
range(V)
Cooling
Heating
Type of
input
Min
Max
Evaporating
Temp. [°C]
Operation
rate
Condensing
Temp. [°C]
Operation
rate
C
0
0
0.4
Comp off
0%
Comp off
0%
Analog
input
1
0.6
1.4
Comp off
Comp off
2
1.6
2.4
Comp off
Comp off
3
2.6
3.4
11.0
40%
31.3
40%
4
3.6
4.4
9.8
45%
33.3
45%
5
4.6
5.4
9.0
50%
34.5
50%
6
5.6
6.4
7.2
60%
37.5
60%
7
6.6
7.4
5.9
70%
40.4
70%
8
7.6
8.4
5.0
80%
43.1
80%
9
8.6
9.4
4.1
90%
45.6
90%
10
9.6
10
3.1
100%
48.1
100%
D
0
0
0.4
No control
-
No control
-
Analog
input
1
0.6
1.4
3.1
100%
48.1
100%
2
1.6
2.4
4.1
90%
45.6
90%
3
2.6
3.4
5.0
80%
43.1
80%
4
3.6
4.4
5.9
70%
40.4
70%
5
4.6
5.4
7.2
60%
37.5
60%
6
5.6
6.4
9.0
50%
34.5
50%
7
6.6
7.4
9.8
45%
33.3
45%
8
7.6
8.4
11.0
40%
31.3
40%
9
8.6
9.4
Comp off
0%
Comp off
0%
10
9.6
10
All off
0%
All off
0%
E
0
0
0.4
Comp off
0%
Comp off
0%
Analog
input
1
0.6
1.4
11.0
40%
31.3
40%
2
1.6
2.4
9.8
45%
33.3
45%
3
2.6
3.4
9.0
50%
34.5
50%
4
3.6
4.4
7.2
60%
37.5
60%
5
4.6
5.4
5.9
70%
40.4
70%
6
5.6
6.4
5.0
80%
43.1
80%
7
6.6
7.4
4.1
90%
45.6
90%
8
7.6
8.4
3.1
100%
48.1
100%
9
8.6
9.4
3.1
48.1
10
9.6
10
3.1
48.1
Содержание PWFCKN000