6
INSTALLATION SCENE
ENGLISH
Signal
Pipe
Thermistor
6
8
9
7
2
4
3
1
5
Air flow
Refrigerant flow
(Cooling)
Refrigerant flow
(Heating)
10
Parts and components
No.
Name
Remarks
1
Air Handling Unit
Field supply
2
Outdoor Unit
Multi V
3
AHU Communication Kit(PRCKA1)
-
4
AHU EEV Kit(PRLK048A0/PRLK096A0)
-
5
Field piping
Field supply
Wiring connections
6
Communication Kit Wiring
Power supply and communication
between comm. kit and outdoor unit
7
Pipe thermistors
(EBG61287703/EBG61287704)
Temp. sensing for refrigerant pipe
8
Room thermistor (EBG36949303)
Temp. sensing for room temp.
9
Remote controller(PQRCVSL0
/ PQRCVSL0QW)
Optional accessory
10
Dry contact(PQDSBNGCM1)
Optional accessory
CAUTION
For Installation of Room thermistor (No. 8), always install that to the inlet of Heat Exchanger.
Otherwise, it may cause to be not operating properly.
!