ACU IO INSTALLATION
7
ENGLISH
Installation Method
1
When installing the ACU IO, please fix and install using Din Rail
(Example of Installation)
2
It should be setting address. (Address Setting : SW02)
Din Rail
ACU IO INSTALLATION
Model
PEXPMB300 (ACU.UIO)
Address
SW02
DIP S/W No.
1
2
3
4
60
ON
1
2
3
4
OFF OFF OFF OFF
61
ON
1
2
3
4
OFF OFF ON OFF
62
ON
1
2
3
4
OFF ON OFF OFF
63
ON
1
2
3
4
OFF ON ON OFF
64
ON
1
2
3
4
ON OFF OFF OFF
65
ON
1
2
3
4
ON OFF ON OFF
66
ON
1
2
3
4
ON ON OFF OFF
67
ON
1
2
3
4
ON ON ON OFF
Model
PEXPMB200 (ACU.UO)
Address
SW02
DIP S/W No.
1
2
3
4
80
ON
1
2
3
4
OFF OFF OFF OFF
81
ON
1
2
3
4
OFF OFF ON OFF
82
ON
1
2
3
4
OFF ON OFF OFF
83
ON
1
2
3
4
OFF ON ON OFF
84
ON
1
2
3
4
ON OFF OFF OFF
85
ON
1
2
3
4
ON OFF ON OFF
86
ON
1
2
3
4
ON ON OFF OFF
87
ON
1
2
3
4
ON ON ON OFF
Model
PEXPMB100 (ACU.UI)
Address
SW02
DIP S/W No.
1
2
3
4
70
ON
1
2
3
4
OFF OFF OFF OFF
71
ON
1
2
3
4
OFF OFF ON OFF
72
ON
1
2
3
4
OFF ON OFF OFF
73
ON
1
2
3
4
OFF ON ON OFF
74
ON
1
2
3
4
ON OFF OFF OFF
75
ON
1
2
3
4
ON OFF ON OFF
76
ON
1
2
3
4
ON ON OFF OFF
77
ON
1
2
3
4
ON ON ON OFF
NOTE
!
• This product should be installed in an enclosure. The enclosure must grounding.
• When factory shipped, DIP Switch is all OFF state.
• Address of same model should be different otherwise it is not work.
• It should be fixed 'OFF' about DIP S/W No.4 otherwise it is not work.