Connecting the ACS IV Controller to the ACS
IO

A maximum of 16 ACS IO’s can be connected
to a single ACS IV Controller.
When there are multiple ACS IO, RS-485 com-
munication cable must be installed using the
daisy chain method.
Failure to do so may cause the ACS IV
Controller to malfunction.

ACS IO Address Creation

When one ACS IV Controller(AC Smart IV,
ACP IV) is connected to multiple ACS IO, to
classify each module a unique address must
be used by selecting rotary switches.

Using the ACS IO rotary switch a 16 digit
between 01~F7 can be created.

(00 addresses may not be created because
they are used for broadcasting at MODBUS
communications.)

Numbers 20~2F are recommended for creat-
ing an ACS IO address.

A maximum of 16 ACS IO can be connected.

Recommended address

• Recommended address  range : 20~2F
• Valid address range : 01~F7

AO1

AO2

AO3 AO4

DO1

DO2

DO3

DI1

DI2

DI3

UI1

UI2

UI3

UI4

AC Smart IV

ACP IV

ACS IV Controller

AO1

AO2

AO3 AO4

DO1

DO2

DO3

DI1

DI2

DI3

UI1

UI2

UI3

UI4

ACS IV Controller

<Correct example: Connection to the RS-485 BUS type>

<Incorrect example: Connection to the RS-485 STAR type>

ACP IV

AC Smart IV

ACS IO Module

AO1

AO2

AO3 AO4

DO1

DO2

DO3

DI1

DI2

DI3

UI1

UI2

UI3

UI4

ACS IO Module

AO1

AO2

AO3 AO4

DO1

DO2

DO3

DI1

DI2

DI3

UI1

UI2

UI3

UI4

ACS IO Module

AO1

AO2

AO3 AO4

DO1

DO2

DO3

DI1

DI2

DI3

UI1

UI2

UI3

UI4

ACS IO Module

AO1

AO2

AO3 AO4

DO1

DO2

DO3

DI1

DI2

DI3

UI1

UI2

UI3

UI4

ACS IO Module

AO1

AO2

AO3 AO4

DO1

DO2

DO3

DI1

DI2

DI3

UI1

UI2

UI3

UI4

ACS IO Module

ACS IO Module

AO1

AO2

AO3 AO4

DO1

DO2

DO3

DI1

DI2

DI3

UI1

UI2

UI3

UI4

ACS IO Module

AO1

AO2

AO3 AO4

DO1

DO2

DO3

DI1

DI2

DI3

UI1

UI2

UI3

UI4

ACS IO Module

AO1

AO2

AO3 AO4

DO1

DO2

DO3

DI1

DI2

DI3

UI1

UI2

UI3

UI4

ACS IO Module

AO1

AO2

AO3 AO4

DO1

DO2

DO3

DI1

DI2

DI3

UI1

UI2

UI3

UI4

ACS IO Module

AO1

AO2

AO3 AO4

DO1

DO2

DO3

DI1

DI2

DI3

UI1

UI2

UI3

UI4

ACS IO Module

CAUTION

• The maximum allowed communication

length for the RS-485 cable is 1 000 m. 
Meaning, that the furthest away an
ACS IO can be installed is 1 000 m
from the ACS IV Controller.

• It is suggested to use 18/2 AWG twist-

ed shielded pair cable.

!

20

Group 

number 

Module 

number 

Group 

number 

Module 

number 

AO1

AO2

AO3 AO4

DO1

DO2

DO3

DI1

DI2

DI3

UI1

UI2

UI3

UI4

ACS IO Module

Address : 0x20

Address : 0x21

Address : 0x22

Address : 0x2F

AC Smart IV

ACP IV

ACS IV Controller

AO1

AO2

AO3 AO4

DO1

DO2

DO3

DI1

DI2

DI3

UI1

UI2

UI3

UI4

ACS IO Module

AO1

AO2

AO3 AO4

DO1

DO2

DO3

DI1

DI2

DI3

UI1

UI2

UI3

UI4

ACS IO Module

AO1

AO2

AO3 AO4

DO1

DO2

DO3

DI1

DI2

DI3

UI1

UI2

UI3

UI4

ACS IO Module

AO1

AO2

AO3 AO4

DO1

DO2

DO3

DI1

DI2

DI3

UI1

UI2

UI3

UI4

ACS IO Module

CAUTION

• Please create a unique address for each

module.

• Do not create an address with 00.

(00 addresses may not be created because
they are used for broadcasting MODBUS
communications.)

• After changing the address be sure to cycle

power.  

!

1,MFL69157012,영영  2017. 7. 14.  영영 3:05  Page 11

Содержание PEXPMB000

Страница 1: ...se retain this installation manual for future reference after reading it thoroughly PEXPMB000 Original instructions HVAC I O module ACS I O Module ENGLISH PORTUGUÊS MALTI MAGYAR SLOVENČINA БЪЛГАРСKN SLOVENŠČINA SRPSKI LATVIEŠU VALODA HRVATSKI LIETUVIŲ KALBA SVENSKA GAEILGE NORSK МАКЕДОНСКИ SUOMI SHQIP DANSK ÍSLENSKA EESTI KEEL BOSANSKI ITALIANO ESPAÑOL FRANÇAIS DEUTSCH ΕΛΛΗΝΙΚΆ ČEŠTINA NEDERLANDS ...

Страница 2: ...nter Disassembly or repair by an unauthorized person may result in fire or electric shock Install the product in an area shielded from rain If water gets into the product it may malfunction Do not install the product in a humid area If the product is damp it may malfunction For installation of the product please contact the dealer from where you purchased the prod uct or a service center Installat...

Страница 3: ...mponents Use of an unauthorized product may result in fire electric shock explosion injury or a malfunction ing of the product If the product has been submerged in water you should contact a service center It may cause a fire or electric shock Do not shock the product The product may malfunction Do not store or use any combustible gas or flammable substances near the product It may cause a fire or...

Страница 4: ...water or insects from getting into the product If a foreign substance gets inside it may cause an electric shock or the product may malfunction Use Clean the product with a soft cloth but not with a solvent based detergent The use of a solvent based detergent may cause a fire or deform the product Do not touch the panel using a pointy or sharp object It can result in an electric shock or the produ...

Страница 5: ... the product is covered by the European Directive 2002 96 EC 2 All electrical and electronic products should be disposed of separate ly from the municipal waste stream via designated collection facili ties appointed by the government or the local authorities 3 The correct disposal of your old appliance will help prevent potential negative consequences for the environment and human health 4 For mor...

Страница 6: ... RUN LED 485 LED Tx Rx Power source LED Input output status LED ACS IO Module AO Port control signal interconnect UI Port control signal interconnect Expansion connector Not used DO Port control signal interconnect DI Port control signal interconnect RS 485 Communication unit 24 V Power input port Dip Switch Not used Rotary Switch ACS IO address creation CAUTION When expanding on the product using...

Страница 7: ...DI3 UI1 UI2 UI3 UI4 ACS IO Module 155 mm 126 mm 70 mm AO1 AO2 AO3 AO4 DO1 DO2 DO3 DI1 DI2 DI3 UI1 UI2 UI3 UI4 ACS IO Module AC24V L N Tx Rx GND CAN ACS IO Installation Manual Installation screws NOTE Components or options may differ from the actual product picture If the supply cord is damaged it must be replaced by the manufacturer its service agent or similarly qualified persons in order to avoi...

Страница 8: ...m and a height of 7 5 mm Follow the instructions below to install the ACS IO in a suitable location First decide a suitable place to install the ACS IO Make sure it is a place that is suitable for connecting the IO power source CAN and RS 485 cables Install the DIN Rail in a place suitable for connecting IO power and RS 485 cables Place the upper part of the ACS IO on the DIN Rail Make sure you ca...

Страница 9: ...dule DO1 DO2 DO3 DI1 DI2 DI3 AO1 AO2 AO3 AO4 UI1 UI2 UI3 UI4 AC 24V L N Tx Rx GND CA N Connecting the product The illustration below shows all the cable connections of the ACS IO Relay On Off output Analog voltage output Universal Voltage current resistance digital input dry only Digital Input Dry Only BUS A BUS B Transformer Power supply 24 V ACS IV Controller N L ACS IO Module Illustration of AC...

Страница 10: ...consumption of the field devices must be considered When power source must be sup plied after completely connecting the product CAUTION Polarity exists when connecting the RS 485 cable therefore when con necting the two cables caution must be taken so that they are not switched Transformer 24 V L Live N Neutral N L ACS IO Module Connecting the communication Link Connecting the RS 485 communication...

Страница 11: ...1 UI2 UI3 UI4 ACS IO Module AO1 AO2 AO3 AO4 DO1 DO2 DO3 DI1 DI2 DI3 UI1 UI2 UI3 UI4 ACS IO Module AO1 AO2 AO3 AO4 DO1 DO2 DO3 DI1 DI2 DI3 UI1 UI2 UI3 UI4 ACS IO Module ACS IO Module AO1 AO2 AO3 AO4 DO1 DO2 DO3 DI1 DI2 DI3 UI1 UI2 UI3 UI4 ACS IO Module AO1 AO2 AO3 AO4 DO1 DO2 DO3 DI1 DI2 DI3 UI1 UI2 UI3 UI4 ACS IO Module AO1 AO2 AO3 AO4 DO1 DO2 DO3 DI1 DI2 DI3 UI1 UI2 UI3 UI4 ACS IO Module AO1 AO2 ...

Страница 12: ...ash twice in 2 seconds When error occurs in ACS IOs 2 though 16 it will flash 3 times every 2 seconds 2 Power source LED This is used to confirm the condition of the power source supply LED is ON while power is applied Otherwise LED is OFF 3 This is used to label the status of each port Refer to port descriptions for details of each of the lights 4 485 communication LED Tx Rx This is used to confi...

Страница 13: ...ble below shows the valid configu ration values for each of four UI ports ACS IO Module Input GND ACS IO Module CAUTION The maximum output possible for switching through digital output is 30 V 30 V and the maximum current is 2 A Deviating from the intended range can cause the product to be damaged CAUTION Using input other than the conditions of use list above can cause product damage and malfunct...

Страница 14: ... of the connector head before attempting to terminate wiring The maximum output current is 20 mA Types of LED input Minimum value Analog Input NTC 10k OFF PT 1000 OFF Ni 1000 OFF DC Voltage OFF DC Current OFF Digital Input Binary Dry contact When there is an input value ON Output GND ACS IO Module Minimum Maximum Voltage 0 V 10 V LED status AO port The input status LED will light up under the foll...