Setting and using method
Installation manual
15
ENGLISH
14
Dry contact for thermostat
Setting and using method
Set desired temperature using Universal Input
n
Change a desired temperature using universal input value
: the voltage(DC 2.5 V~8.5 V) or resistance(2.5~8.5 kΩ) value of external controller or devices through
universal input port can be applied desired temperature value(18~30 °C).
Voltage
or
Resistance
Voltage (+)
Voltage (-)
Target Temperature (℃)
Target Temperature(℉)
Input Resistance (kΩ)
Input Voltage (DC V)
18
64
2.5
2.5
19
66
3.0
3.0
20
68
3.5
3.5
21
70
4.0
4.0
22
72
4.5
4.5
23
74
5.0
5.0
24
76
5.5
5.5
25
76
6.0
6.0
26
78
6.5
6.5
27
80
7.0
7.0
28
82
7.5
7.5
29
84
8.0
8.0
30
86
8.5
8.5
Notes
• When this function is enabled, value of TEMP_SW is ignored.
• When using resistance type input, it possible to occur ±2 ℉(±1 ℃) tolerance by internal voltage source
environment.
SETTING_SW
Function
Off
On
SW 1
Universal Input
Disable
Enable
SW 2
Universal Input Type
Voltage
Resistance
SW 3
Temperature Tracking
Disable
Enable
SW 4
-
-
-
SW 5
Tracking delta Temperature
SW 6
SW 7
Tracking Period Time
SW 8
SW 5
SW 6
SET VALUE
OFF
OFF
±8 ℉ (±4 ℃)
ON
OFF
±6 ℉ (±3 ℃)
OFF
ON
±4 ℉ (±2 ℃)
ON
ON
±2 ℉ (±1 ℃)
SW 7
SW 8
SET VALUE
OFF
OFF
3 minutes
ON
OFF
5 minutes
OFF
ON
10 minutes
ON
ON
20 minutes
Installation of thermostat
n
When interlocking with thermostat, select the option of
control function as described below.
OPER_SW
TEMP_SW
<Switch Function>
TEMP_SW
OPER_SW
Thermostat mode
WIND Signal en/disable
F
0
Conventional AC Unit Thermostat
Disable
1
Enable
2
Heat Pump Thermostat_O
Terminal
Disable
3
Enable
4
Heat Pump Thermostat_B
Terminal
Disable
5
Enable
1) When interlocking with thermostat, set TEMP_SW to F.
2) Enable CN_WIND signal – Amount of wind flow(Low, Middle, High) signal enable
Notes
• Information of ‘OPER_SW’ is sensed only initial step by Dry contact module therefore , once the
configuration changed , Reset of Dry contact module is required.
• After power input or unit’s reset , wait 25~30 seconds(Display LED 10 times blinking) for unit
stabilization then Dry contact module will operate normally.
• Do not use desired temperature setting function when interlocking with thermostat.