Installation Manual
31
ENGLISH
System set-up
You can add, edit or delete the indoor unit
• When adding an air conditioner :
When you click on
the window, you will see the yellow entry window.
Enter the type, air conditioner name, physical address,
model name and maximum power consumption.
• When editing an air conditioner :
Select the air
conditioner to edit and make changes.
• When deleting an air conditioner :
Press the
of
the air conditioner to delete.
Air conditioner information entry
Adding, editing or deleting outdoor unit
(4) Air conditioner information entry & temporary save window
Type
■
UAC: Integrated air conditioner (MultiV PLUS, MPS product, others
applied with LGAP)
■
SGL for special model, Don't select SGL
Units
■
Click on the air conditioner to add or edit and you will see the yellow
entry window where you can edit the name.
Address
■
When you press the Default entry button, it will succeed the higher
information and automatically generate the default values.
■
The first and second number indicates the G/W number and outdoor
unit number, and they can only be edited within the information entered
in the existing [G/W information] and [outdoor unit information].
The third number, the indoor unit (air conditioner) number, cannot be
duplicated within the same outdoor unit number and must be within the
range of (0-15).
Model
Base - Default
Maximum power consumption
Set by each model.
By setting the maximum power consumption value of the air conditioner,
the system limits the power consumption within the set limit.
Note:
For peak control, you must enter the maximum power consumption
for each indoor unit.
Air conditioner information entry