Functions
2.1 Oil Return/Defrost Control
2.2 Liquid Bypass Control
2.3 Subcooling EEV Control
Target : about 25°C
Subcooling EEV works with Fuzzy rules to keep the degree of subcooling at the outlet of subcooler during
simultaneous operation
The degree of subcooler = T outlet of subcooler – T inlet of subcooler
Open or Close
Close
Keep
High pressure gas valve
Close
Open
60 Hz
Running
Ending
Starting
Component
40 Hz
Stop
Inverter compressor
Open or Close
Keep
Low pressure gas valve
Close
Open for 30s
Balancing valve
Are whole indoor units
operating
cooling mode?
Solenoid valve open
for liquid bypass
(High pressure gas
→
Low pressure gas valve)
Indoor units operating
Yes
No
2. Special Control