36
Outdoor Unit
Pipe connections between indoor and outdoor unit
u
Combination of Y branch/header method
1 Outdoor Units
Example : 5 Indoor Units connected
Ⓐ
: Outdoor Unit
Ⓑ
: 1st branch (Y branch)
Ⓒ
: Y branch
Ⓓ
: Indoor Unit
Ⓔ
: Header
Ⓕ
: Sealed piping
L 492ft(150m)(656ft(200m) : Conditional application)
131ft(40m)(295ft(90m) : Conditional application)
L
361ft(1
1
0m)
49ft(15m)
Branch pipe can not be used after header
Branch pipe can not be used after header
2 Outdoor Units
Example : 5 Indoor Units connected
Ⓐ
: Outdoor Unit
Ⓑ
: 1st branch
Ⓒ
: Y branch
Ⓓ
: Indoor Unit
Ⓔ
: Connection branch pipe be-
tween Outdoor units:
ARCNN21
Ⓕ
: Header
Ⓖ
: Sealed piping
33ft
(10m)
or less
H 361ft(1
10m)
49ft(15m)
Master
Slave
Master
Slave
Master
Slave
L 492ft(150m)(656ft(200m) : Conditional application)
131ft(40m)(295ft(90m) : Conditional application)
ODU Capacity
Master Slave