Table 4: 575V, 60Hz, 3-Phase Multi V Water V
For component model numbers, see the specification tables.
For 575V systems, acceptable voltage range is 518V - 632V.
Maximum allowable voltage unbalance is 2%.
MCA = Minimum Circuit Ampacity.
Maximum Overcurrent Protection (MOCP) is calculated as follows: (Largest motor RLA x 2.25) + (Sum of
other motor RLA) rounded down to the nearest standard fuse size.
Nom.
Tons
System
Model No.
Compressor (Comp.)
MCA
MOCP
Comp.
Qty.
Motor RLA (Ea.)
Frame 1 Frame 2 Frame 3 Frame 1 Frame 2 Frame 3
Frame 1 Frame 2 Frame 3
6.0 ARWM072CAS5
1
7.1
–
–
8.9
–
–
15
–
–
8.0 ARWM096CAS5
1
7.6
–
–
9.5
–
–
15
–
–
10.0 ARWM121CAS5
1
9.3
–
–
11.7
–
–
20
–
–
12.0 ARWM144CAS5
1
11.6
–
–
14.5
–
–
25
–
–
16.0 ARWM192CAS5
1
14.2
–
–
17.8
–
–
30
–
–
20.0 ARWM240CAS5
2
7.6
11.6
–
14.5
9.5
–
25
15
–
24.0 ARWM289CAS5
2
11.6
11.6
–
14.5
14.5
–
25
25
–
28.0 ARWM337CAS5
2
14.2
11.6
–
17.8
14.5
–
30
25
–
36.0 ARWM432CAS5
3
11.6
11.6
11.6
14.5
14.5
14.5
25
25
25
40.0 ARWM480CAS5
3
14.2
11.6
11.6
17.8
14.5
14.5
30
25
25
48.0 ARWM576CAS5
3
14.2
14.2
14.2
17.8
17.8
17.8
30
30
30
Multi V Water V 575V Unit Specifications
ELECTRICAL DATA
Multi V Water V 575V Models
Nominal Cooling
(Btu/h)
Indoor Units
Max. Qty.
Sum of Indoor Unit Nominal Cooling Capacities (Btu/h)
Min. Capacity (Btu/h) (50%)
1
Max. Capacity (Btu/h) (130%)
2
ARWM072CAS5
72,000
13
36,000
93,600
ARWM096CAS5
96,000
16
48,000
124,800
ARWM121CAS5
119,700
20
60,000
156,000
ARWM144CAS5
144,000
23
72,000
187,200
ARWM192CAS5
192,000
32
96,000
249,600
ARWM240CAS5
239,400
39
120,000
312,000
ARWM288CAS5
287,700
45
144,000
374,400
ARWM336CAS5
336,000
55
168,000
436,800
ARWM432CAS5
430,500
64
216,000
561,600
ARWM480CAS5
472,500
64
240,000
624,000
ARWM576CAS5
571,200
64
288,000
748,800
Table 5: Multi V Water V 575V Unit / Indoor Unit Matching Limitations
CONNECTION LIMITATIONS
1
50% = Minimum Combination Ratio.
2
130% = Maximum Combination Ratio.
Water Source Units