36
Outside Unit
Refrigerant piping system
Branch pipe can not be used after header
3. When installing 3 outside units
Ex) 5 Indoor Units connected
Ⓐ
: Outside Units
Ⓑ
: 1st branch(Y branch)
Ⓒ
: Y branch
Ⓓ
: Indoor Unit
Ⓔ
: Connection branch pipe between Outside
units:ARCNN30
Ⓕ
: Connection branch pipe between Outside
units:ARCNN20
Ⓖ
: Header
Ⓗ
: Sealing
Master
Slave2
Slave1
10m or
less
H Below 50m
L150m
l
40m
Below 2m
Below 2m
(h1)
(h1)
Below 2m
(h1)
Ú
Slave1 outside unit ~ Connecting
branch pipe
Ⓔ
: Pipe diameter
between outside units (E)
Ú
Connecting branch pipe
Ⓔ
~ 1st Y
branch part
Ⓑ
: Main pipe diameter (A)
Ú
Refrigerant pipe diameter from branch
to branch (B, C)
Ú
Total refrigerant pipe length =
A + B + C + a + b + c + d + e ≤ 300m (500m**)
Total capacity of indoor units
connected to after branching (kW)
≤ 5.6
Ø6.35
Ø12.7
< 16
Ø9.52
Ø15.88
< 22.4
Ø9.52
Ø19.05
< 33
Ø9.52
Ø22.2
< 47
Ø12.7
Ø28.58
< 71
Ø15.88
Ø28.58
< 104
Ø19.05
Ø34.9
104 ≤
Ø19.05
Ø41.3
Liquid pipe
(mm)
Gas pipe
(mm)
For the first branch pipe (B), use the branch pipe
that fits the main pipe diameter (A).
Longest pipe length (Equivalent pipe length)
A +B +b,A +C +e ≤ 150 m(175 m)
Longest pipe length after 1st branching
B +b,C +e ≤ 40 m
High/Low difference (Outside unit
÷
Indoor unit)
H
≤
50 m
High/Low difference (Indoor unit
÷
Indoor unit)
h
≤
15 m
High/Low difference (Indoor unit
÷
Indoor unit)
h
≤
2 m
L
ℓ
H
h
h1
Liquid pipe (mm) Gas pipe (mm)
Low/high pressure
common pipe(mm)
Ø15.88/19.05
Ø34.9/41.3
Ø19.05
Ú
Slave2 outside unit ~ Connecting
branch pipe
Ⓕ
: Pipe diameter
between outside units (F)
Liquid pipe (mm) Gas pipe (mm)
Low/high pressure
common pipe(mm)
Ø9.52/12.7
Ø22.2/28.58
Ø19.05
Outside unit capacity
Liquid pipe (mm)
Gas pipe (mm)
42, 44, 46, 48, 50, 52,
54, 56, 58, 60HP
Ø 19.05
Ø 41.3