background image

8

Indoor Unit

Installation

Ceiling dimension and hanging bolt location

Level gauge

Ceiling

Ceiling board

1,028 (Ceiling opening)

923 (Hanging bolt)

344(Hanging bolt)

860

55

50

410

53

53

450 (Ceiling opening)

(unit: mm)

• The dimensions of the paper model for installation are the same as those of the ceiling opening dimensions.

• Avoid the following installation location.
1. Such places as restaurants and kitchen where considerable amount of oil steam and flour is generated.

These may cause heat exchange efficiency reduction, or water drops, drain pump mal-function.
In these cases, take the following actions;

• Make sure that ventilation fan is enough to cover all noxious gases from this place.
• Ensure enough distance from the cooking room to install the air conditioner in such a place where it may

not suck oily steam.

2. Avoid installng air conditioner in such

places where cooking oil or iron powder is
generated.

3. Avoid places where inflammable gas is

generated.

4. Avoid place where noxious gas is 

generated.

5. Avoid places near high frequency 

generators.

NOTICE

CAUTION :
• This air-conditioner uses a drain

pump.

• Install the unit horizontally using a

level gauge.

• During the installation, care should

be taken not to damage electric
wires.

• Select and mark the position for fixing bolts and piping hole.
• Decide the position for fixing bolts slightly tilted to the drain

direction after considering the direction of drain hose.

• Drill the hole for anchor bolt on the wall.

Use the ventilation fan
for smoke-collecting
hood with sufficient
capacity.

Cooking table

Air conditioner

Take enough
distance

Содержание MULTI V TJ Series

Страница 1: ...ead this installation manual completely before installing the product Installation work must be performed in accordance with the national wiring standards by authorized personnel only Please retain this installation manual for future reference after reading it thoroughly ENGLISH ITALIANO ESPAÑOL FRANÇAIS DEUTSCH ...

Страница 2: ...ll Horizontal meter Flaring tool set Specified torque wrenches different depending on model No Spanner Half union Hexagonal wrench Gas leak detector Vacuum pump Gauge manifold Owner s manual Thermometer Installation Parts 3 Safety Precautions 4 Installation Selection of the best location7 Ceiling dimension and hang ing bolt location 8 Wiring Connection 9 Installation of Decoration Panel 10 Drain P...

Страница 3: ...Air Intake Air Outlet Installation Parts Name Quantity Shape for gas pipe for liquid pipe Clamp metal 2 EA Insulation for fitting 1 SET Drain hose 1 EA Plastic band 8 EA Washer for hanging backet 4 EA Other Paper pattern for installation Owner s manual Installation manual ...

Страница 4: ...he possibility of injury or damage to properties only Be sure not to do Be sure to follow the instruction Installation Do not use a defective or under rated circuit breaker Use this appliance on a dedicated circuit There is risk of fire or electric shock For electrical work contact the dealer seller a qualified electri cian or an Authorized Service Center Do not disassemble or repair the product T...

Страница 5: ...l of the case edges and the fins on the condenser and evaporator For installation always contact the dealer or an Authorized Service Center There is risk of fire electric shock explosion or injury Do not install the product on a defective installation stand It may cause injury accident or damage to the product Be sure the installation area does not deteriorate with age If the base collapses the ai...

Страница 6: ...t To avoid vibration or water leakage Do not install the product where the noise or hot air from the out door unit could damage the neighborhoods It may cause a problem for your neighbors Use two or more people to lift and transport the product Avoid personal injury Do not install the product where it will be exposed to sea wind salt spray directly It may cause corrosion on the product Corrosion p...

Страница 7: ...ar the door way Ensure the spaces indicated by arrows from the wall ceiling or other obstacles The indoor unit must have the maintenance space Read completely then follow step by step Unit cm Ceiling Ceiling Board Ceiling Board 20 or more Above 250 330 or less 100 or more 50 or more 50 or more 30 or less Floor Installation Selection of the best location CAUTION In case that the unit is installed n...

Страница 8: ... enough distance from the cooking room to install the air conditioner in such a place where it may not suck oily steam 2 Avoid installng air conditioner in such places where cooking oil or iron powder is generated 3 Avoid places where inflammable gas is generated 4 Avoid place where noxious gas is generated 5 Avoid places near high frequency generators NOTICE CAUTION This air conditioner uses a dr...

Страница 9: ... The following parts are local purchasing Hanging Bolt W 3 8 or M10 Nut W 3 8 or M10 Spring Washer M10 Plate Washer M10 Terminal Block Indoor 1 L 2 N 3 4 INDOOR POWER INPUT Indoor unit Outdoor unit Central controller A B E F C D Vcc GND Main outdoor unit Connect the wires to the terminals on the control board individually according to the outdoor unit connection Ensure that the color of the wires ...

Страница 10: ...ll the air inlet grille including the air filter Piping side Decorative panel fixing screws Hexagon M6 screw Air conditioner unit Decorative panel Push Decorative panel fixing screws hexagon M6 screws Temporarily fitting at 2 poles Tightening about 10mm Inlet Grille Inlet Grille Inlet Grille Key holes Louver motor Control box cover Cover Ratch pull Plasma filter The decoration panel has its instal...

Страница 11: ... end Feed water to the flexible drain hose and check the piping for leakage Be sure to check the drain pump for normal operating and noise when electrical wiring is complete When the test is complete connect the flex ible drain hose to the drain port on the indoor unit Heat insulation material Polyethylene foam with thick ness more than 8 mm Drain test Flexible drain hose Maintenance drain port Up...

Страница 12: ... to burn out of the wires 4 Specification of power source 5 Confirm that electrical capacity is sufficient 6 Be sure that the starting voltage is maintained at more than 90 percent of the rated voltage marked on the name plate 7 Confirm that the cable thickness is as specified in the power sources specification Particularly note the relation between cable length and thickness 8 Never fail to equip...

Страница 13: ...e room thmperature sensor is in the indoor unit the remote controller should be installed in such places away from direct sunlight and high humidity Installation of the remote controller Select places that are not splashed with water Select controller position after receiving customer approval The room temperature sensor is built in the indoor unit This remote controller equipped with liquid cryst...

Страница 14: ...cover of the wired remote controller to set the mode 2 Select one of three selectable modes as follows Position 1 The room temperature is controlled by the thermistor of the main body Position 2 The room themperature is controlled by the thermis tor of the wired remote controller control the temper ature according to the position of wired remote con troller Position 3 The room temperature is contr...

Страница 15: ...P No 3828A20873C Printed in Korea After reading this manual keep it in a place easily accessible to the user for future reference ...

Отзывы: