Installation Manual
35
Refrigerant piping installation
Branch pipe can not be used after header
3 Outdoor Units
Example : 5 Indoor Units connected
: Outdoor Unit
: 1st branch(Y branch)
: Y branch
: Indoor Unit
: Connection branch pipe
between Outdoor units:
ARCNN30
: Connection branch pipe
between Outdoor units:
ARCNN20
: Header
: Sealing
10m or
less
H 100m
L 150m
40m
Master
Slave2
Slave1
Branch pipe can not be used after header
3 Outdoor Units
Example : 5 Indoor Units connected
: Outdoor Unit
: 1st branch(Y branch)
: Y branch
: Indoor Unit
: Connection branch pipe
between Outdoor units:
ARCNN30
: Connection branch pipe
between Outdoor units:
ARCNN20
: Header
: Sealing
10m or
less
H 100m
L 150m
40m
Master
Slave2
Slave1