50
Outdoor Unit
Electrical Wiring
■
Using Cool/Heat Selector Installation and Connection
• Connect wires as below figure at the hole of backside of Outdoor Unit Dry Contact.
• Insert the wire in the connection hole pushing the "Push" button.
• Maximum transmission line length for dry contact : 200m.
Mode Change
Push Button
Heating
Outdoor Unit
Fan
Cooling
Cool/Heat Selector Installation and Connection(Heat pump only)
■
Without Cool/Heat Selector Installation and Connection
In case, try to set mode without Cool/Heat Selector and try to use other switch except from LG Outdoor
Cool/Heat Selector in field.
Connect signal terminal block as below figure and description.
- How to set mode without Cool/Heat Selector
• Cooling Mode Setting
➀ ➔
GND Connection
➁ ➔
Off (Open)
• Heating Mode Setting
➀ ➔
GND Connection
➁ ➔
GND Connection
• Fan Mode Setting
➀ ➔
Off (Open)
➁ ➔
GND Connection
GND
GND
GND