TI V Ceiling Cassette Indoor Units
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
GENERAL DATA
6SHFL¿FDWLRQV
Model No.
ARNU183TSA4
ARNU243TSA4
Cooling Mode Performance
Capacity (Btu/h)
19,100
24,200
Max. Power Input
1
(W)
70
70
L/M/H Power Input at Factory Default (W)
24 / 29 / 34
25 / 30 / 40
Heating Mode Performance
Capacity (Btu/h)
21,500
27,300
Max. Power Input
1
(W)
70
70
L/M/H Power Input at Factory Default (W)
24 / 29 / 34
25 / 30 / 40
Entering Mixed Air
Cooling Max (°F WB)
76
76
Heating Min (°F DB)
59
59
Unit Data
Refrigerant Type
2
R410A
R410A
Refrigerant Control
EEV
EEV
Sound Pressure
3
dB(A) (H/M/L)
35 / 33 / 31
40 / 37 / 33
Net Unit Weight (lbs.)
39.9
39.9
Shipping Weight (lbs.)
49.6
49.6
Grille Weight (lbs)
10.3
10.3
Grille Shipping Weight (lbs)
14.3
14.3
Communication Cable
4
(No. x AWG)
2 x 18
2 x 18
Fan
Type
Turbo Fan
Turbo Fan
Quantity
1
1
Motor/Drive
Brushless Digitally Controlled / Direct
Airflow Rate H/M/L (CFM)
459 / 424 / 353
601 / 530 / 459
Piping
Liquid Line (in., O.D.)
1/4 Flare
3/8 Flare
Vapor Line (in., O.D.)
1/2 Flare
5/8 Flare
Condensate Line (in., I.D.)
1
1
Table 5: Two-Way Ceiling Cassette (TS Frames) Indoor Unit General Data.
EEV: Electronic Expansion Valve
3RZHUZLULQJLV¿HOGVXSSOLHGDQGPXVWFRPSO\ZLWKWKHDSSOLFDEOHORFDODQGQDWLRQDO
codes. See page 18 for detailed electrical data.
This unit comes with a dry nitrogen charge.
All capacities are net with a combination ratio between 95-105%.
5DWHGFDSDFLW\LVFHUWL¿H5,6WDQGDUG5DWLQJVDUHVXEMHFWWRFKDQJH
ZLWKRXWQRWLFH&XUUHQWFHUWL¿HGUDWLQJVDUHDYDLODEOHDWZZZDKULGLUHFWRU\RUJ
1
Max. power input is rated at maximum setting value.
2
Take appropriate actions at the end of HVAC equipment life to recover, recycle, reclaim or
destroy R410A refrigerant according to applicable regulations (40 CFR Part 82, Subpart F)
under section 608 of CAA.
3
Sound Pressure levels are tested in an anechoic chamber under ISO Standard 3745.
4
Communication cable between Main ODU to IDUs / HRUs to be 18 AWG, 2-conductor,
twisted, stranded, shielded. Ensure the communication cable shield is properly grounded
to the Main ODU chassis only. Do not ground the ODU to IDUs / HRUs communication
cable at any other point. Wiring must comply with all applicable local and national codes.