28
ENGLISH
Example) Connection of communication cable
[BUS type]
[STAR type]
- Connection of communication
cable must be installed like
below figure between indoor
unit to outdoor unit.
- Abnormal operation can be
caused by communication
defect, when connection of
communication cable is installed
like below figure(STAR type).
It should be wiring power cables or communication cables to avoid
interference with the oil level sensor. Otherwise, That oil level sensor
would be operated abnormally.
Example) Connection of power and communication cable (UXA)
Gap : Over
50 mm(1.97’’)
When connecting
Main power lines
/ Ground wire from left side
When connecting
Communication wires
/ Ground wire from left side
Main power
terminal block
Ground wire
Main power
terminal block
Insulation sleeves
attachments
Ground wire
Ground wire
ODU-IDU
Communication
cable
ODU-ODU
Communication
cable
Bottom Side
Main power
terminal block
Ground wire
When connecting
Communication wires
/ Ground wire from
front guide panel
When connecting
Main power lines
/ Ground wire from
front guide panel
Gap : Over
50 mm(1.97’’)
Front Side
Fix firmly with cable tie or
clamp cord not to be displaced
Main power line
connection
Communication/Ground
wire connection
Master
Outdoor Unit
SODU. B SODU. A
IDU. B
IDU. A
CEN. B
CEN. A
DRY1
DRY2
GND
12V
SODU. B SODU. A
IDU. B
IDU. A
CEN. B
CEN. A
DRY1
DRY2
GND
12V
SODU. B SODU. A
IDU. B
IDU. A
CEN. B
CEN. A
DRY1
DRY2
GND
12V
Master
Outdoor Unit
SODU. B SODU. A
IDU. B
IDU. A
CEN. B
CEN. A
DRY1
DRY2
GND
12V
Slave1
Outdoor Unit
Slave2
Outdoor Unit
3(A) 4(B)
3(A) 4(B)
3(A) 4(B)
3(A) 4(B)
A
B
Between Indoor and Master Outdoor unit
• It is not the point to make ground connection.
- Make sure that terminal number of master and slave outdoor units
are matched. (A-A,B-B)
Main power
terminal block
Ground wire
When connecting
Communication wires
/ Ground wire from
front guide panel
When connecting
Main power lines
/ Ground wire from
front guide panel
Gap : Over
50 mm(1.97’’)
Front Side
Fix firmly with cable tie
or clamp cord not to be
displaced
Example) Connection of power and communication cable (UXB)
Main power
terminal block
Ground wire
Gap : Over
50 mm(1.97’’)
When connecting
Main power lines
/ Ground wire from left side
When connecting
Communication wires
/ Ground wire from left side
Bottom Side
CAUTION
!
1,MFL67221443,영영 19. 1. 31. 영영 11:48 Page 28