ALTERNATIVE REFRIGERANT R410A

The refrigerant R410A has the property of higher operating pressure in
comparison with R22.  
Therefore, all materials have the characteristics of higher resisting
pressure than R22 ones and this characteristic should also be consid-
ered during the installation. 
R410A is an azeotrope of R32 and R125 mixed at 50:50, so the ozone
depletion potential (ODP) of R410A is 0.

CAUTION

• The above list indicates the order in which the individual work

operations are normally carried out but this order may be varied
where local conditions warrants such change.

• The thickness of the piping should comply with the relevant

local and national regulations for the designed pressure 3.8 MPa
(551.1 psi).

• Since R410A is a mixed refrigerant, the required additional re-

frigerant must be charged in its liquid state.(If the refrigerant is
charged in its gaseous state, its composition changes and the
system will not work properly.)

!

CAUTION

Notes : * We can guarantee the operation only within 130%

combination. If you want to connect more than 130%
combination, please contact us and discuss the re-
quirement like below.

• If the operation of indoor unit is more than 130%, the airflow

will be operated as low in the all indoor units.

Combination Ratio(50~200%)

Outdoor Number

Connection Ratio

Single outdoor units

200%

Double outdoor units

160%

Triple outdoor units

130%

Over the triple unit 

130%

!

CAUTION

• The wall thickness of the piping should comply with the relevant

local and national regulations for the designed pressure 3.8MPa
[551.1psi]

• Since R410A is a mixed refrigerant, the required additional re-

frigerant must be charged in its liquid state. 
If the refrigerant is charged in its gaseous state, its composition
changes and the system will not work properly.

• Do not place the refrigerant container under the direct rays of

the sun to prevent it from exploding.

• For high-pressure refrigerant, any unapproved pipe must not be

used.

• Do not heat pipes more than necessary to prevent them from

softening.

• Be careful not to install wrongly to minimize economic loss be-

cause it is expensive in comparison with R22.

!

OUTDOOR UNITS INFORMATION

The foundation must be level even

Outdoor unit foundation work

Avoid short circuits and ensure 
sufficient space is allowed for service

Installation of outdoor unit

Refer to automatic addressing flowchart

Automatic addressing of indoor unit 

In the final check for 24hours at 3.8MPa (38.7 kgf/cm

2

)[551.1psi]

there must be no drop in pressure.

Airtight test

Multiple core cable must not be used.
(suitable cable should be selected)

Electrical work

(connection circuits and drive circuits)

Make sure no gaps are left where 
the insulating materials are joined

Heat insulation work

Make sure airflow is sufficient

Duct work

Adjust to downward gradient

Drain pipe work

Special attention to dryness, 
cleanness and tightness

Refrigerant piping work

Check model name to 
make sure the fitting 
is made correctly

Installation of indoor unit

Take account of gradient 
of drain piping

Sleeve and insert work

Make connection clearly between outdoor, indoor, 
remote controller and option.

Preparation of contract drawings

Indicate clearly who will be responsible for switch setting.

Determination of division work

The vacuum pump used must have a capacity of reaching at least 
5 torr, more than 1 hour

Vacuum drying

Recharge correctly as calculated in this manual. and record the 
amount of added refrigerant

Additional charge of refrigerant

Make sure there are no gaps left between the facing materials 
used on the ceiling 

Fit facing panels

Run each indoor unit in turn to make sure the pipe work 
has been fitted correctly

Test run adjustment

Explain the use of the system as clearly as possible to your customer and 
make sure all relevant documentation is in order

Transfer to customer with explanation

Preheat the crank case with the electrical  heater for more than 6 hours.

INSTALLATION PROCESS

1,MFL67221438,영영  2018. 10. 4.  영영 11:29  Page 5

Содержание MULTI V 5 ARUN100BTE5

Страница 1: ...efore installing the product Installation work must be performed in accordance with the national wiring standards by authorized personnel only Please retain this installation manual for future reference after reading it thoroughly Heat Pump Original instruction MFL67221438 Rev 00_092118 ENGLISH ESPAÑOL PORTUGUÊS 1 MFL67221438 영영 2018 10 4 영영 11 29 Page 1 ...

Страница 2: ...t refrigerant from the refrigerant speci fied on the unit If a different refrigerant or air is mixed with the original refrigerant the refrigerant cycle may malfunction and the unit may be dam aged Do not reconstruct to change the settings of the protection devices If the pressure switch thermal switch or other protection device is shorted and operated forcibly or parts other than those speci fied...

Страница 3: ...erminals Inadequate connection and fastening may generate heat and cause a fire Be sure the installation area does not deteriorate with age If the base collapses the air conditioner could fall with it causing property damage product failure or personal injury Install and insulate the drain hose to ensure that water is drained away properly based on the installation manual A bad connection may caus...

Страница 4: ...ethods 11 REFRIGERANT PIPING INSTALLATION 11 Precautions on Pipe connection Valve operation 11 Connection of Outdoor units 11 Caution 12 PIPE CONNECTIONS BETWEEN INDOOR AND OUTDOOR UNIT 12 Preparation Work 13 Pipe Drawing Out during Single Series connection 13 Refrigerant piping system 14 Pipe Connection Method between outdoor unit indoor unit 16 Branch pipe Fitting 18 Distribution Method 18 Vacuu...

Страница 5: ...ressure refrigerant any unapproved pipe must not be used Do not heat pipes more than necessary to prevent them from softening Be careful not to install wrongly to minimize economic loss be cause it is expensive in comparison with R22 OUTDOOR UNITS INFORMATION The foundation must be level even Outdoor unit foundation work Avoid short circuits and ensure sufficient space is allowed for service Insta...

Страница 6: ...B 500 19 11 16 C 50 1 31 32 D 500 19 11 16 E 100 3 15 16 F 900 35 7 16 A 10 13 32 B 500 19 11 16 C 10 13 32 D 500 19 11 16 E 20 25 32 F 1800 70 7 8 A 50 1 31 32 B 500 19 11 16 C 50 1 31 32 D 500 19 11 16 E 100 3 15 16 F 1200 47 1 4 Only 2 sides are walls A 10 13 32 B 300 11 13 16 A 10 13 32 B 300 11 13 16 E 20 25 32 500 19 11 16 D F E G 500 19 11 16 D H H F E G 500 19 11 16 D H F E I G 500 19 11 1...

Страница 7: ...s under the unit and use the two suspension points each at the front and rear Always lift the unit with ropes attached at four points so that impact is not applied to the unit Attach the ropes to the unit at an angle of 40 or less Locking points for transportation ropes Forklift Carrying Guide Forklift Carrying Hole LIFTING METHOD CAUTION Be very careful while carrying the product Do not have only...

Страница 8: ... Ⓔ H beam support Ⓕ Concrete support CAUTION Be sure to remove the Pallet Wood Support of the bottom side of the outdoor unit Base panel before fixing the bolt It may cause the unstable state of the outdoor settlement and may cause freezing of the heat exchanger resulting in abnormal oper ations Be sure to remove the Pallet Wood Support of the bottom side of the outdoor unit before welding Not rem...

Страница 9: ...0 76 19 7 0 78 CAUTION Always use a charge hose for service port connection After tightening the cap check that no refrigerant leaks are present When loosening a flare nut always use two wrenches in combination When connecting the piping always use a spanner and torque wrench in combination to tighten the flare nut When connecting a flare nut coat the flare inner and outer faces with oil for R410A...

Страница 10: ...is formed on the internal piping The oxide film is a caused by clogging EEV Capillary oil hole of accu mulator and suction hole of oil pump in compressor It prevents normal operation of the compressor In order to avoid this problem Welding should be done after replacing air by nitrogen gas When welding plumbing pipe the work is required Always use the nitrogen not use oxygen carbon dioxide and a C...

Страница 11: ...ranch A B To outdoor unit To branch piping or indoor unit A B Facing upwards Facing downwards Within 3 Within 3 Viewed from point A in direction of arrow Within 10 2 Commercially available piping often contains dust and other materi als Always blow it clean with a dry inert gas 3 Use care to prevent dust water or other contaminants from entering the piping during installation 4 Reduce the number o...

Страница 12: ...s and do not use flux If not oxidized film can cause clogging or dam age to the compressor unit and flux can harm the copper piping or refrigerant oil A B WARNING When installing and moving the air conditioner to another site be sure to make recharge refrigerant after perfect evacuation If a different refrigerant or air is mixed with the original refriger ant the refrigerant cycle may malfunction ...

Страница 13: ...pe between Outdoor units ARCNN31 Ⓖ Connection branch pipe between Outdoor units ARCNN21 Y branch method Slave3 Slave2 Slave1 Master Indoor Unit l 40 m 131 ft 90m 295 ft H 110 m 361 ft L 150 m 492 ft 200 m 656 ft h 40 m 131 ft 10m or less ODU Capacity Master Slave 1 Slave 2 Slave 3 F E G C C C C C h See Table 4 Series Outdoor Units 2 Units 4 Units Combination of Y branch header Method Ⓐ Outdoor Uni...

Страница 14: ...eter from outdoor unit to first branch A ODU capacity hp Pipe diameter when pipe length is 90m 295ft Standard Pipe diameter when pipe length is 90m 295ft Pipe diameter when height differ ential ODU IDU is 50m 164ft Liquid Pipe mm inch Gas Pipe mm inch Liquid Pipe mm inch Gas Pipe mm inch Liquid Pipe mm inch Gas Pipe mm inch 8 Ø9 52 3 8 Ø19 05 3 4 Ø12 7 1 2 Ø22 2 7 8 Ø12 7 1 2 Not increased 10 Ø9 5...

Страница 15: ... units is 10 m 32 8 ft or less Pipes between outdoor units are 2 m 6 6 ft or less 2 m 6 6 ft or less If the distance between the outdoor units becomes more than 2 m 6 6 ft apply Oil Traps between the gas pipes If the outdoor unit is located lower than the main pipe apply Oil Trap Pipes between outdoor units are 2 m 6 6 ft or longer Oil Trap Oil Trap Oil Trap 2 m 6 6 ft or less 2m 6 6ft orless 2m 6...

Страница 16: ...r of the refrigerant piping selected by the procedures described is different from the size of the joint the connecting sec tion should be cut with a pipe cutter Branch pipe should be insulated with the insulator in each kit Branch pipe Fitting When the number of indoor units to be connected to the branch pipes is less than the number of branch pipes available for connec tion then cap pipes should...

Страница 17: ...52 3 8 I D 9 52 3 8 I D 6 35 1 4 ARBLN23220 O D 28 58 1 1 8 I D 22 2 7 8 115 4 17 32 X2 100 4 11 32 O D 15 88 5 8 I D 12 7 1 2 70 2 3 4 O D 22 2 7 8 I D 15 88 5 8 I D 19 05 3 4 120 4 23 32 O D 38 1 1 1 2 I D 34 9 1 3 8 I D 28 58 1 1 8 O D 44 48 1 3 4 X2 175 6 7 8 I D 31 8 1 1 4 I D 53 98 2 1 4 I D 25 4 1 I D 44 48 1 3 4 I D 44 48 1 3 4 I D 38 1 1 1 2 I D 41 3 1 5 8 I D 44 48 1 3 4 I D 38 1 1 1 2 I...

Страница 18: ...id side Gas side Close Close Close Close When inserting nitrogen gas of high pressure it must be used with reg ulator This function is used for creating vacuum in the system after compres sor replacement ODU parts replacement or IDU addition replacement Vacuum mode setting method SW01C Ɨ Confirm Automatic Addressing SW02C ȭ backward SW04C X cancel DIP SW01 7 Segment SW01D reset SW03C ȯ forward Vac...

Страница 19: ...amount of refrigerant For the refrigerant addi tional charge Too much or too little refrigerant will cause trouble To use the Vacuum Mode If the Vacuum mode is set all valves of Indoor units and Outdoor units will be opened WARNING Use a vacuum pump or Inert nitrogen gas when doing leakage test or air purge Do not compress air or Oxygen and do not use Flamma ble gases Otherwise it may cause fire o...

Страница 20: ...on system or building ventilation sys tem Limitation in piping work Prepare for earthquake and thermal stress Volume of the room at which Indoor Unit of the least capacity is installed Total amount of refrigerant in the system 0 44 kg m3 0 028 lbs ft3 Attach the additional refrigerant table of IDU Bad example Do not insulate gas or low pressure pipe and liquid or highpres sure pipe together Be sur...

Страница 21: ...t box of Indoor and Outdoor Units because the box is sometimes removed at the time of service work Never connect the main power source to terminal block of communi cation cable If connected electrical parts will be burnt out Use the 2 core shielded wires for communication cable mark in the figure below If communication cable of different systems are wired with the same multiplecore cable the resul...

Страница 22: ...cable When none are available follow the instructions below Do not connect wiring of different thicknesses to the power terminal block Slack in the power wiring may cause abnormal heat When connecting cable which is the same thickness do as shown in the figure below For wiring use the designated power cable and connect firmly then secure to prevent outside pressure being exerted on the terminal bl...

Страница 23: ...loping due to interference in the signal wiring caused by electrostatic and elec tromagnetic coupling The tables below indicates our recommendation as to appropriate spacing of communication and power cables where these are to be run side by side Communication and Power Cables Communication cable Types shielded wires or unshielded wires Cross section 1 0 1 5 mm2 1 55 10 3 2 32 10 3 in2 Maximum all...

Страница 24: ...0V 50Hz 380 415V 220 240V Wiring of main power supply and equipment capacity Use a separate power supply for the Outdoor Unit and Indoor Unit Bear in mind ambient conditions ambient temperature direct sun light rain water etc when proceeding with the wiring and connec tions The cable size is the minimum value for metal conduit wiring The power cord size should be 1 rank thicker taking into account...

Страница 25: ...ely from the power supply Install the main switch that can interrupt all the power sources in an integrated manner because this system consists of the equipment utilizing the multiple power sources If there exists the possibility of reversed phase lose phase mo mentary blackout or the power goes on and off while the product is operating attach a reversed phase protection circuit locally Running th...

Страница 26: ...nes Ground wire from front guide panel Gap Over 50mm 1 97 Front Side Fix firmly with cable tie or clamp cord not to be displaced Main power line connection Communication Ground wire connection Quick control Setting In the factory setting main PCB dip switch setting is all OFF Check and make sure that all the indoor unit model name are ARNU 4 Change the main PCB Dip switch No 3 OFF ON like below pi...

Страница 27: ... power supply is not applied to the indoor unit operation error occur Automatic Addressing has to be performed after more than 3 min utes to improve indoor unit communition when initial power is sup plied Please be sure that all the dip switch 1 7 of master outdoor unit is OFF before Automatic Addressing setting Setting the optional function Select the mode function option value using Button and c...

Страница 28: ...6 on on oFF Central Control Con nection at Indoor Unit side Fn 19 oFF oFF on Compressor Input Current Limit mode Fn 20 oFF oFF oP1 oP10 Power Consump tion Display on wired remote con troller Fn 21 SPL0 SPL0 SPL1 Pd10 Pd11 Overall Defrost Op erating in Low tem perature Heating Fn 22 oFF on oFF Optional Base panel Heater Fn 23 oFF on oFF User Idu Comfort Cooling Mode setting Id 10 EAch Refer Com for...

Страница 29: ...0 op4 op6 op11 52 56 57 op7 op9 op12 49 53 55 CAUTION Request installer to set the function during installation If ODU RPM changes cooling capacity may go down Master unit PCB DIP switch on No 5 Select the mode using Button Func Push the button Select the Function using Button Fn4 Push the button Select the Option using Button on oFF Push the button Overall defrost mode is set Mode setting on Oper...

Страница 30: ...ect the Option using Button on oFF Push the button Low Ambient Kit Mode setting method h Reference for functional logic of I O Module CAUTION Ask an authorized technician to setting a function If do not use a function set an off mode Change a power consumption or capacity Setting Mode Purpose Condensing temperature variation Evaporating temperature variation Heat Cool op1 Increase capacity Increas...

Страница 31: ...1 Push the button Select the Option using Button oFF op1 op5 Push the button Auto Dust Removal Mode is set Function setting Setting Inverter Hz oFF op1 143 Hz op2 135 Hz op3 128 Hz op4 120 Hz op5 113 Hz op6 105 Hz op7 98 Hz op8 90 Hz op9 83 Hz CAUTION Ask an authorized technician to setting a function If use a function first install a Central controller Master unit PCB DIP switch on No 5 Select th...

Страница 32: ... temperature wll be decreased When used heating operation in case of high humidity condition de forest will be delayed because target high low pressure will be changed Master unit PCB DIP switch on No 5 Select the mode using Button Func Push the button Select the Function using Button Fn16 Push the button Select the Option using Button Fn19 Push the button Select the Option using Button on oFF Pus...

Страница 33: ...g capacity mid Power consumption mid 3 Cooling capacity high Power consumption high Master unit PCB DIP switch on No 5 Select the mode using Button Idu Push the button Select the Function using Button Id10 Push the button EEV pulse appearing seg1 seg2 Idu No seg3 seg4 Mode Select the Function using Button Idu No setting and Push the button Select the Function using Button Mode setting and Push the...

Страница 34: ...ror outdoor unit indoor unit Failing to receive outdoor unit signal in indoor unit PCB 0 6 Outlet pipe temperature sensor of indoor unit Outlet pipe temperature sensor of indoor unit is open or short 0 8 Hydro Kit Hot water storage tank Temperature sensor Pipe temperature sensor is open or short 0 9 Indoor EEPROM Error In case when the serial number marked on EEPROM of Indoor unit is 0 or FFFFFF 1...

Страница 35: ...S T power of Outdoor Unit Omitting connection of outdoor unit 5 1 Excessive capacity of indoor units Excessive connection of indoor units compared to capacity of Out door Unit 5 2 Communication error inverter PCB Main PCB Failing to receive inverter signal at main PCB of Outdoor Unit 5 3 Communication error indoor unit Main PCB of Outdoor Unit Failing to receive indoor unit signal at main PCB of O...

Страница 36: ... 1 5 1 Failure of operation mode conversion at Outdoor Unit Failure of operation mode conversion at Outdoor Unit 1 5 3 Outdoor Unit Heat Exchanger Temperature Sen sor upper part Fault Outdoor Unit Heat Exchanger Temperature Sensor upper part Fault 1 5 4 Outdoor Unit Heat Exchanger Temperature Sen sor lower part Fault Outdoor Unit Heat Exchanger Temperature Sensor lower part open or short 1 8 2 Out...

Страница 37: ...ows out CAUTION FOR REFRIGERANT LEAK The installer and system specialist shall secure safety against leakage according to local regulations or standards The following standards may be applicable if local regulations are not available Introduction Though the R410A refrigerant is harmless and incombustible itself the room to equip the air conditioner should be large to such an extent that the refrig...

Страница 38: ... areas where corrosive gases such as acid or alkaline gas are produced Avoid installing the product where it could be exposed to sea wind salty wind directly It can result corrosion on the product Corrosion particularly on the condenser and evaporator fins could cause product malfunction or inefficient operation If outdoor unit is installed close to the seaside should avoid direct exposure to the ...

Страница 39: ...lizar o descarte ade quado de parelhos celulares pilhas e baterias 3 Através do Programa Coleta Inteligente a LG disponíbiliza pontos de coleta em localidades diversas incluindo assistências técnicas autorizadas da LG Electron ics Para mais informações visite o site www lge com br coleta seletivaou contate nosso SAC através do número 4004 5400 Capitais e Regiòs metropolitanas ou 0800 707 5454 dema...

Отзывы: