1. Specification
Note:
1. Capacities are based on the following conditions:
Cooling: - Indoor Temperature 26.7˚C(80˚F) DB/19.4˚C(67˚F)
- Outdoor Temperature 35˚C(95˚F) DB/23.9˚C(75˚F)
Heating: - Indoor Temperature 21.1˚C(70˚F) DB/15.6˚C(60˚F) WB
- Outdoor Temperature 8.3˚C(47˚F) DB/6.1˚C(43˚F) WB
Piping Length - Interconnecting Piping Length 7.5m(24.6 ft.)
- Level Difference of Zero
2. Wiring cable size must comply with the applicable local and national code.
3. The specification may be subject to change without prior notice for purpose of improvement.
4. For more Capacity(*),refer to the combination table
Conversion Formula
kW = Btu/h class X 0.0002931
cfm = CMM x 35.3
Power Supply
Ø / V / Hz
Capacity(*)
Btu/h class
Current
Running Current
A
Fan
Motor Type
Fan Type
Motor Output(W) x No. of Unit
Air Flow Rate
CMM
(H / M / L)
CFM
External Static Pressure
mmAq
Capacitor
µF / Vac
Drive
Coil
Row x Column x FPI
Dimensions Body
mm(inch)
(W x H x D)
Decorative Panel
mm(inch)
Net Weight
Body
kg (lbs)
Decorative Panel
kg (lbs)
Air Filter
Sound Level (H / M / L)
dB(A)+3
Piping
Liquid
mm (inch)
Connections
Gas
mm (inch)
Drain(OD/ID)
mm(inch)
Dehumidification Rate
l/h
Safety Devices
Temperature Sensor
Referigerant
Referigerant Control
Transmission Interunit Cable
No. x AWG
Model
Decoration Panel Name
AMNW12GTRA0[LMCN125HV]
PT-UQC
AMNW18GTQA0[LMCN185HV]
PT-UQC
Indoor unit type
Ceilling Cassette - 4way
1/ 208~230/ 60
1/ 208~230/ 60
12,000
18,000
0.25
0.25
BLDC
BLDC
Turbo Fan
Turbo Fan
43 x 1
43 x 1
9.5/ 8/ 7
13/ 12/ 11
335/282/247
459/424/388
-
-
-
-
Direct Drive
Direct Drive
2R x 8C x 18
2R x 10C x 18
570 x 214 x 570 ( 22 7/16 x 8 7/16 x 22 7/16) 570 x 256 x 570 ( 22 7/16 x 10 x 22 7/16)
700 x 30 x 700 (27 6/19 x 1 3/16 x 27 6/19) 700 x 30 x 700 (27 6/19 x 1 3/16 x 27 6/19)
14 (30.9)
15 (33.1)
3 (6.6)
3 (6.6)
Long life filter
Long life filter
38/ 35/ 32
38/ 37/ 34
6.35 (1/4)
6.35 (1/4)
9.52 (3/8)
12.7 (1/2)
32 / 25(1.26/0.984)
32 / 25(1.26/0.984)
2
2
Fuse, thermal protector for fan motor Fuse, thermal protector for fan motor
Thermistor
Thermistor
R410A
R410A
EEV(in Outdoor unit)
EEV(in Outdoor unit)
4X18(Including Earth)
4X18(Including Earth)