Addre
ss
NO.
Description
Default
Maximu
m
Minimu
m
Unit
5325
FU2 #37
Inertia rate
0
1
0
5327
FU2 #39
Carrier freq
50
150
10
0.1kHZ
5328
FU2 #40
Control mode
0
2
0
5329
FU2 #41
Auto tuning
0
1
0
532A
FU2 #42
Rs (Note5)
(Note4)
5000
0
0.001oh
m
532B
FU2 #43
Rr (Note6)
(Note4)
5000
0
0.001oh
m
532C
FU2 #44
Lsigma (Note7)
(Note4)
MaxInd
uc
0
0.001m
H
532D
FU2 #45
SL P-gain
32767
32767
0
532E
FU2 #46
SL I-gain
3276
32767
0
532F
FU2 #47
proc PI mode
0
1
0
5330
FU2 #48
PID Ref
1
1
0
5331
FU2 #49
PID Ref Mode
0
5
0
5332
FU2 #50
PID Out Dir
1
1
0
5333
FU2 #51
PID F/B
0
2
0
5334
FU2 #52
PID P-gain
3000
9999
0
0.1%
5335
FU2 #53
PID I-time
300
320
0
0.1sec
5336
FU2 #54
PID D-time
0
9999
0
0.1msec
5337
FU2 #55
PID +limit
6000
maxFre
q
0
0.01Hz
17