INSTALLATION OF OUTDOOR UNIT
ENGLISH
7
INSTALLATION OF OUTDOOR UNIT
Installation Places
Unit : mm(inch)
Piping length and the elevation
If installed tube is shorter than 7.5 m(24.6 ft), additional refrigerant charging is not necessary.
Additional Refrigerant = [A -7.5 m(2.46 ft)] x Additional refrigerant [g(oz)]
* In case of A-Coil combination, Charge additional refrigerant
ex) If installed tube is shorter than 7.5 m(24.6 ft), Charge additional refrigerant for A-Coil Combination
[g(oz)]
ex) If installed tube is more than 7.5 m(24.6 ft),
Total Additional Refrigerant = { [A -7.5 m(2.46 ft)] x Additional refrigerant [g(oz)] } + additional refrigerant
fot A-Coil Combination [g(oz)]
More than
300(11.8)
Fence or
obstacles
More than 700(27.6)
Awning
More than 600(23.6)
More than
More than
300(11.8)
300(11.8)
More than
300(11.8)
- If an awning is built over the unit to prevent
direct sunlight or rain exposure, make sure
that heat radiation from the condenser is not
restricted.
- Ensure that the spaces indicated by arrows
around front, back and side of the unit.
- Do not place animals and plants in the path
of the warm air.
- Take the air conditioner weight into account
and select a place where noise and vibration
are minimum.
- Select a place so that the warm air and noise
from the air conditioner do not disturb
neighbors.
Outdoor unit
Indoor unit
A
B
Outdoor unit
Indoor unit
A
B
CAPACITY
(kBtu/h)
Pipe Size mm(inch)
Length A Unit : m(ft)
Elevation B Unit : m(ft)
Additional
refrigerant
Unit : g/m(oz/ft)
A-Coil Combination
Additional refrigerant
*
Unit : g(oz)
Gas
Liquid
Standard
Max.
Standard
Max.
18
Ø 15.88(5/8)
Ø 9.52(3/8)
7.5(24.6)
50(164)
5(16)
30(98)
40(0.43)
-
500(17.6)
24
Ø 15.88(5/8)
Ø 9.52(3/8)
7.5(24.6)
50(164)
5(16)
30(98)
40(0.43)
-
200(7.1)
36
Ø 15.88(5/8)
Ø 9.52(3/8)
7.5(24.6)
75(246)
5(16)
30(98)
40(0.43)
-
-
42
Ø 15.88(5/8)
Ø 9.52(3/8)
7.5(24.6)
75(246)
5(16)
30(98)
40(0.43)
-
-
48
Ø 15.88(5/8)
Ø 9.52(3/8)
7.5(24.6)
75(246)
5(16)
30(98)
40(0.43)
-