–17–
[Air inlet side view]
The power cord connected to the outdoor unit should be complied
with the following specifications (Rubber insulation, type H05RN-F
approved by HAR or SAA).
If the supply cord is damaged, it must be replaced by a special cord or assembly available from the manufacturer or its service agent.
The connecting cable connected to the indoor and outdoor unit should
be complied with the following specifications (Rubber insulation,
type H05RN-F approved by HAR or SAA).
CAUTION
8.5mm
20mm
GN/YL
7.5mm
20mm
GN/YL
NORMAL
CROSS-SECTIONAL
AREA 0.75mm
2
NORMAL
CROSS-SECTIONAL
AREA 2.5mm
2
(24K)
Control box cover
Indoor
power cord
Remote
controller
cord
Control box cover
fitting screw(2 units)
Terminal Block of Indoor Unit
3(L) 4(N)
5
6
7
1(L) 2(N)
3(L) 4(N)
5
6
7
8
Terminal Block of Outdoor Unit
Power Cord
Terminal Block of Indoor Unit
3(L) 4(N)
5
6
7
1(L) 2(N)
3(L) 4(N)
5
6
7
8
Terminal Block of Outdoor Unit
Power Cord
5. Wiring Connection
• Open the control box cover and connect the Remote controller cord and Indoor power wires.
Make sure that the screws of the terminal are free from looseness.
WARNING
• 24K, 1 Phase
Cooling Model
• 24K, 1 Phase
Heat Pump