–18–
1. All wiring must comply with LOCAL REGULATIONS.
2. Select a power source that is capable of supplying the current required by the air conditioner.
3. Feed the power source to the unit via a distribution switch board designed for this purpose.
4. The terminal screws inside the control box may be loose due to vibration during transport.
Check the screws for loose connection.
(Running the air conditioner with loose connection can overload and damage electrical components.)
5. Always ground the air conditioner with a grounding wire and connector to meet the LOCAL REGULATION.
Main power source
Switch box
Refrigerant pipe
Circuit Breaker
Use circuit breaker or time delay fuse.
ELECTRICAL WIRING
CONNECTING THE CABLE TO OUTDOOR UNIT
1. Remove the Cover control from the unit by loosening a
screw.
Connect the wires to the terminals on the control
board individually as following.
2. Secure the cable onto the control board with the hold-
er (clamper).
3. Refix the cover control to the original position with the
screw.
4. Use a recongnized circuit breaker 20A between the
power source and the unit. A disconnection device to
adequately disconnect all supply lines must be fitted.
Outdoor unit
Terminal block
(6P)
Connecting
cable
Cover control
Holder for
connecting
cable