Service Manual 55
Troubleshooting Guide
2. Evacuation
(All amount of refrigerant leaked)
• Procedure
(1) Connect the vacuum pump to the center hose
of charge set center hose
(2) Evacuation for approximately one hour.
– Confirm that the gauge needle has moved
toward -76 cmHg (vacuum of 4 mmHg or less).
(3) Close the valve (Lo side) on the charge set,
turn off the vacuum pump, and confirm that
the gauge needle does not move (approxima-
tely 5 minutes after turning off the vacuum
pump).
(4) Disconnect the charge hose from the vacuum
pump.
– Vacuum pump oil.
If the vacuum pump oil becomes dirty or
depleted, replenish as needed.
Lo
Open
Open
Vacuum pump
3-Way
valve
Outdoor unit
Liquid side
Indoor unit
Gas side
3-Way
valve
CLOSE
OPEN
Содержание LS301CE
Страница 47: ...Service Manual 47 Schematic Diagram DISPLAY P W B ASM Model LS301CE LS301HE ...
Страница 48: ...48 Room Air Conditioner Wiring Diagram Schematic Diagram 1 Indoor Unit Cooling Only Models Heating Models ...
Страница 49: ...Service Manual 49 Schematic Diagram 2 Outdoor Unit Cooling Only Models Heating Models ...
Страница 71: ...P No 3828A20390S October 2006 Printed in Korea ...