12 | PRODUCT DATA
Single Zone Mega W
all Mounted Engineering Manual
Due to our policy of continuous product innovation, some specifications may change without notification.
©
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG ” is a registered trademark of LG Corp.
GENERAL DATA
Mega 115V Specifications
Table 3:
Single Zone Mega 115V System Specifications.
System Model Number (IDU/ODU)
LS090HXV (LSN090HXV/LSU090HXV)
LS120HXV (LSN120HXV/LSU120HXV)
Cooling Capacity (Min/Rated/Max) (Btu/h)
1,023 ~ 8,500 ~ 13,785
1,023 ~ 12,000 ~ 13,785
Cooling Power Input
1
(kW)
0.71
1.14
Heating Capacity (Min/Rated/Max) (Btu/h)
1,023 ~ 10,900 ~ 22,178
1,023 ~ 13,000 ~ 22,178
Heating Power Input
1
(kW)
0.88
1.09
COP
3.63
3.50
EER
12.01
10.5
SEER
17.0
17.0
HSPF
9.0
9.0
Power Supply (V/Hz/Ø)
115/60/1
Outdoor Unit Operating Range
Cooling (°F DB)
14 to 118
Heating (°F WB)
14 to 65
Indoor Unit Operating Range
Cooling (°F WB)
53 to 75
Heating (°F DB)
60 to 86
Indoor Temperature Setting Range
Cooling (°F)
65 to 86
Heating (°F)
60 to 86
Unit Data
Refrigerant Type
2
R410A
Refrigerant Control
EEV
IDU Sound Pressure
3
dB(A) (H/M/L/Sleep)
39/33/23/19
39/33/23/19
ODU Sound Pressure
3
dB(A)
47
47
Unit Weight (lbs)
IDU (Net/Shipping)
23/26
23/26
ODU (Net/Shipping)
67/79
67/79
Power/Communication Cable
4
(No. x AWG)
4 x 18
Compressor
Compressor Type (Qty)
Single Rotary (1)
Single Rotary (1)
Fan
IDU Type (Qty)
Cross Flow (1)
ODU Type (Qty)
Propeller (1)
Motor/Drive
Brushless Digitally Controlled/Direct
Airflow Rate
IDU Max/H/M/L (CFM)
335/272/212/124
335/272/212/124
ODU Max (CFM)
1,000
1,000
Piping
Liquid Line (in, OD)
1/4
1/4
Vapor Line (in, OD)
3/8
3/8
Condensation Line (OD, ID)
27/32, 5/8
27/32, 5/8
Additional Refrigerant Charge (oz/ft)
0.22
0.22
Pipe Length
5
(Minimum/Maximum)(ft)
6.6 / 49.2
6.6 / 49.2
Piping Length
5
(no add’l refrigerant, ft)
24.6
24.6
Max Elevation Difference (ft)
23
23
EEV: Electronic Expansion Valve IDU: Indoor Unit ODU: Outdoor Unit
1
Power Input is rated at high speed.
2
Take appropriate actions at the end of HVAC equipment life to recover, recycle, reclaim or destroy
R410A refrigerant according to applicable regulations (40 CFR Part 82, Subpart F) under section 608
of CAA.
3
Sound Pressure levels are tested in an anechoic chamber under ISO Standard 3745.
4
All power wiring/communication cables are field supplied and are to be minimum 18 AWG, 4-conductor,
stranded, shielded and must comply with applicable local and national codes.
5
Piping lengths are equivalent.
This unit comes with a dry helium charge.
This data is rated 0 ft above sea level with 24.6 of refrigerant line per indoor unit and a 0 ft level
difference outdoor and indoor units.
Cooling capacity rating obtained with air entering the indoor unit at 80ºF dry bulb (DB) and 67ºF wet
bulb (WB) and outdoor ambient conditions of 95ºF dry bulb (DB) and 75ºF wet bulb (WB).
Heating capacity rating obtained with air entering the indoor unit at 70ºF dry bulb (DB) and 59ºF wet
bulb (WB) and outdoor ambient conditions of 47ºF dry bulb (DB) and 43ºF wet bulb (WB).