Date:
Job
Name/Location:
PO
No.:
Architect:
Engr:
GC:
Rep:
For:
File
Approval
Mech:
Resubmit
Other
Tag
#:
(Company)
(Project
Manager)
Multi
F
Inverter
Heat
Pump
Outdoor
Unit
DFS
‐
SB
‐
AD
‐
004
‐
US
013A08
Performance:
LMU369HV
Capacity
(Btu/h)
34,000
Cooling
Power
Input
(kW)
2.72
Heating
Power
Input
(kW)
3.58
Cooling
Nominal
Test
Conditions:
Heating
Nominal
Test
Conditions:
Indoor:
80°F
DB/67°F
WB
Indoor:
70°F
DB/60°F
WB
Outdoor: 95°F
DB/75°F
WB
Outdoor: 47°F
DB/43°F
WB
Electrical:
Power
Supply
(V¹/Hz/Ø)
208
‐
230/60/1
MOP
(A)
25
MCA
(A)
16.8
Cooling
Rated
Amps
(A)
18.6
Heating
Rated
Amps
(A)
19.0
Compressor
(A)
12.1
Fan
Motor
(A)
0.55
Piping:
Refrigerant
Charge
(lbs)
7.72
Liquid
Line
(in,
OD)
1/4
(4
Each)
Vapor
Line
(in,
OD)
3/8
(4
Each)
Max
Total
Piping
(ft)²
246.1
Max
Elevation
between
ODU
and
IDU
(ft)
49.2
Max
Elevation
between
IDU
and
IDU
(ft)
24.6
Controls
Features:
•Auto
opera on
•Auto
restart
opera on
•Defrost/Deicing
•Inverter
(variable
speed
compressor)
•Low
ambient
opera on
to
14F
(cooling
mode)
•Restart
delay
(3
‐
minutes)
•Self
diagnosis
•So
start
Operating
Range:
Cooling
(°F
DB)
14
‐
118
Heating
(°F
WB)
0
‐
64
Unit
Data:
Refrigerant
Type
R410A
Refrigerant
Control
EEV
Sound
Pressure
(±3
dB(A))²
57
Net
Unit
Weight
(lbs)
209.4
Shipping
Weight
(lbs)
222.6
Heat
Exchanger
Coating
GoldFin™
Max
Number
of
Indoor
Units
4
Compressor:
Quantity
1
Type
Twin
‐
Rotary
Inverter
Oil/Type
FVC68D
Fan:
Type
Propeller
Quantity
2
Fan
Motor/Drive
Brushless
Digitally
Controlled/Direct
Airflow
Rate
(CFM)
2,119
Standard
Features:
•Limited
Five
Year
Compressor
Warranty
•Limited
Two
Year
Func onal
Parts
Warranty
Notes:
Max
ODU
to
IDU
Piping
(ft)
82.0
Piping
Length
(no
add'l
refrigerant,
ft)
98.4
Communication
Cable
(No.
x
AWG)³
4
X
18
1.Acceptable
opera ng
voltage:
187V
‐
253V.
2.Piping
lengths
are
equivalent.
3.Sound
Pressure
levels
are
tested
in
an
anechoic
chamber
under
ISO
Standard
1996.
4.All
communica on
cable
to
be
minimum
18
AWG,
2
‐
conductor,
stranded,
shielded
and
must
comply
with
applicable
local
and
national
code.
5.See
Engineering
Manual
for
sensible
and
latent
capaci es.
6.Power
wiring
cable
size
must
comply
with
the
applicable
local
and
na onal
code.
7.This
data
is
rated
0
above
sea
level,
with
24.6
of
refrigerant
line
and
a
0
level
difference
between
outdoor
and
indoor
units.
All
capacities
are
net
with
a
combination
ratio
between
95
–
105%.
8.Must
follow
installa on
instruc ons
in
the
applicable
LG
installa on
manual.
Min
Number
of
Indoor
Units
2
For
continual
product
development,
LG
reserves
the
right
to
change
specifications
without
notice.
LG
Electronics
U.S.A.,
Inc.,
Englewood
Cliffs,
NJ.
All
rights
reserved.
“LG
Life’s
Good”
is
a
registered
trademark
of
LG
Corp.
/www.lghvac.com
Optional
Accessories:
PI
‐
485
Integration
Board
(PMNFP14A0)
AC
Smart
II
(PQCSW320A1E)
AC
Ez
(PQCSZ250S0)
MOP
‐
Maximum
Overcurrent
Protection MCA
‐
Minimum
Circuit
Ampacity
ODU
‐
Outdoor
Unit
IDU
‐
Indoor
Unit
AWG
‐
American
Wire
Gage
Page
1
of
5