- 43 -
No
5
Checking flow
Damper checking method.
Inputting TEST Mode,
Check the damper and PCB.
6
Check the Fan motor.
Rotate fan using your hand.
Stuck change the motor.
(Cause of ice or rust inside of motor)
Result & SVC Action
(1)
(3)
(2)
(4)
Open
Closed
Not
working
1 Mode
2 Mode
1,2
mode
Damper is normal.
(Go to 6)
Change the damper
Test
Mode
Damper
State
SVC Action
(1) to (2)
(3) to (4)
270 ~330
Other
270 ~330
Other
It’s normal
Change damper
It’s normal
Change damper
Point
Result
SVC Action
Below 12 V
0 or 5 V
(2) ~ (3)
(1) ~ (3)
Change the PCB
Change the motor
Point
Result
SVC Action
Sticky
Not Sticky
Motor
Change the motor
Go to 7
Point
Result
SVC Action
<CON6>
(1)Pin1, (2)Pin3, (3)Pin5
7
Check the R Fan motor voltage.